Addressable Fire Panel IRIS - Installation and Programming Manual 53
6. APPENDIX
Appendix A - Possible error messages
Text Messages Description
Аlarm Fire signal from detector.
Loop Device Type Error A different than the expected type of device has been detected at the address.
Loop Device Fault The device does not respond (lost or damaged).
Double Address More than one device with the same address in the loop.
PreAlarm Fire signal from detector in 2DEVICES zone.
Evacuate Activated Call Point or EVACUATE button on the panel.
Loop Device Input Fault Fault in loop device input.
Loop Device Output Fault Fault in loop device output.
Loop Device Sounder Fault Fault in loop sounder output (short-circuit or interruption).
Fault Routing - Fault Fault at problem output (short-circuit or interruption).
Fire Brigade - Fault Fault at re output (short-circuit or interruption).
Fire Protection - Fault Fire protection fault (short-circuit or interruption).
Loop Device Disabled Loop device has been disabled.
Chamber Faul Fault in the detector.
Clean Me Now Dirty detector chamber.
Test Fire Fire signal from tested detector.
Signal Blockage Signal blockage in linear detector.
Hi Signal Too high a signal in linear detector.
Drift Alert Sensor compensation limit reached.
Earth Fault Resistive connection between some signals and earth < 10k.
Battery Low Low battery.
Charger Fault Fault in the charging device.
Battery Loss Loss of electric battery supply.
AC Loss Loss of mains supply.
Sounder Fault Fault at sounder output (short-circuit or interruption).
AUX24V Fault Short-circuit.
AUX12V Fault Short-circuit.
Periphery Device Fault The device does not respond (lost or damaged).
Periphery Device Type Error A different than the expected type of device has been detected at the address.
External Power Supply Fault
External power supply fault (low battery, loss of battery, charger fault, loss of mains or
earth leak).
External Power Supply Loss Loss of external power supply.
Zone Disabled The zone has been disabled.
Zone in Test The zone is in test mode.
Sounder Disabled The sounders have been disabled.
Fire Brigade Output Disabled The re output has been disabled.
Fire Protection Output
Disabled
The re protection has been disabled.
Fault Output Disabled The fault output has been disabled.
Reset Reseting of the panel.
Silence Alarm Sounders silencing.
Ram Error RAM memory error.
Flash Error Flash memory error.
Panel Fault Fault in the connection with another panel (when two or more panels are connected
in a network).
Double IP address Doubling of an IP address.
Double Panel number Doubling of the panel number (when two or more panels are connected in a network).
Double IP address and Panel
number
Doubling of the IP address and the panel number (when two or more panels are con-
nected in a network).
New Periphery Devices Found New periphery devices have been detected.
New Loop Device Found New loop devices have been detected.
Loop Short Short-circuit in the loop.
Loop Break Interrupted loop.
Loop Zero Address There is a device without address number (a device with addres 0 is applied).