Addressable Fire Panel IRIS - Installation and Programming Manual 55
Tables for correspondence of the System Sensor device types.
Devices with no need of type
readjustment.
LED switching on -
ON (BLINK)
1
Maintenance of
day and night time
working modes.
Thresholds
for the FIRE
signal
2
Day / night time for an
alarm conrmation
3
- 1251E (Ionisation sensor) in case of a FIRE signal (1-3)
- 2251EM (Photoelectric smoke sensor) in case of a FIRE signal (1-3)
- 5251EM (Temperature sensor) in case of a FIRE signal -
- 2251TEM (Multi- criteria re sensor) in case of a FIRE signal (1-6)
- 7251 (Photoelectric smoke sensor) in case of a FIRE signal (1-9)
- M210E (Single input) in case of activation at the input / fault - - -
- M201E (Single output) in case of activation at the output / fault - - -
- M512ME (Zone monitor) in case of activation at the input / fault - - -
- CR-6 (Six Relay Control Module) in case of activation at the input / fault - - -
- CZ-6 (Six Zone Interface Module) in case of activation at the input / fault - - -
- IM-10 (Ten Input Monitor Input) in case of activation at the input / fault - - -
1
A specic mode is assigned to the light-emitting diode of the device: BLINK and OFF. In the BLINK mode the LED blinks at every query addressed by the system. In the OFF
mode the LED does not reect any device contact. The LED turns ON in case of a FIRE signal.
2
The device maintains day and night time working modes. Each of these are assigned different times of ltration of the FIRE signal. The night time mode must be less than
that of the daytime mode. For specic cases the times of both modes can be 0, disallowing ltration time, having the re signal is immediately perceived.
3
The devices maintains day and night conrmation of alarm (in seconds). The alarm must remain active during the programmable period of time in order to generate an alarm
event from the panel. If the detector restores its normal state prior to time-out, the panel shall not generate the alarm.