12.2 Component Replacement 
The inverter is composed of various electronic components including semiconductor elements. 
Periodic inspection of the following components is necessary, as their characteristics will change over 
time due to their structure or 
material. This may cause inverter performance to decrease and may lead 
to more serious 
failures. 
1 ) Cooling fan 
The 
lifetime of the cooling fan (used to cool heat-generating components such as the main circuit 
semiconductor elements) is approx. 
30,000 hours (approx. 2 to 3 years of continuous operation). If 
abnormal noise or vibration is detected during a periodic inspection and the fan is determined to be 
the cause, it must be replaced. 
2) 
Smoothing capacitor 
Large-capacity aluminum electrolytic capacitors are used for smoothing 
in 
the main circuit 
DC 
section. 
The characteristics of these capacitors 
will deteriorate over time due to ripple current, etc. The time 
period involved is 
largely dependent upon the ambient temperature and the operating conditions, but 
when operated under normal conditions, replacement 
is 
required approx. every 5 years. 
(On 3.7kW and smaller units, the smoothing capacitors are located on the PCB, so the PCB must also 
be replaced.) 
Capacitor appearance inspection and evaluation standards: 
a) 
Is any fluid leaking? 
b) 
Is the knob (safety valve) protruding or expanded? 
c) 
Measure the capacitance and leakage current. 
* A time guideline for the replacement period of these components can be established by checking the 
cumulative run time monitor. 
Table 
12-1 
Standard component replacement periods 
Part name 
Standard replacement period 
Cooling fan 
2 to 3 years (Approx. 
30,000 hours) 
Smoothing capacitors  5 years 
-111 
-