E6580516 
Note 1) When 
Id 
IS r  I 
in 
G ,-.F (reverse run disable selection) is set to  I , the display will always be: 
:F,--F. 
Note 2) Four monitor elements can be selected by the status monitor display selections 
in 
G 
,-
.Uc 
. 
In 
addition, the display units for current and voltage elements can 
be 
set to 
A, 
V (respectively) or 
%. 
Note 
3) 
The input voltage value displayed is calculated by multiplying 1 /-h times the 
DC 
voltage obtained 
by rectifying the input voltage. 
If the input voltage drops below 1 
OOV, 
the display will be: 
:-=:;---. 
Note 4) The display will be: : 
,0 
- - - when only control power is applied. 
Note 5) The cumulative run time is counted 
only while running. 
(The time 
is 
not counted when the output frequency monitor is displaying 
O.O 
.} 
The value shown 
is 
in 
100-hour units ( O 
O. 
I  - 9 9 9  : 1 hour to 99900 hours} 
When the 
g) 
@) 
keys are held down during the above steps, the display will change to the next item 
every 0.5 sec. The run/stop, frequency display status or settings monitor mode can be entered, and 
terminal input operation mode can be switched to 
(only when stopped} at any point in the process. The 
_.._symbol 
in the example indicates that the left and right symbols are alternately displayed every 0.5 
sec. 
7 .3.3 Setting Monitor Mode 
This mode is entered by pressing the 
I PRGI key 
in 
standard monitor mode. 
To exit this mode, press the 
I PRG I key to move to standard monitor mode, or the I MON I key to move 
to status monitor mode. 
As described 
below, this mode both displays parameters and settings, and contains the setting and 
adjustment functions. 
The 
"Panel Operation Mode Selection" ( 
F' 
rt 
[Id 
in 
C ,- .U 
f:: 
} must be set to  3 
c' 
or 
greater 
in 
order 
to change parameter settings. (The standard 
default setting allows this. } 
The "Panel Operation Mode Selection" parameter can be changed even when set to "parameter 
changes prohibited". 
(1) 
Parameter setting and display function 
Use the following procedure to set the desired parameter value. 
1. 
Press I PRG I to enter setting monitor mode. 
2. At the group title display, press 
g)@) to select the desired group, then press I ENTER I to 
display the group's parameter names. 
3. At the parameter name 
display, press  g)@) to select the parameter name, then press 
I ENTER I to display the data setting. 
4. 
At the data setting display, change the data with the 
g) 
~keys. 
5. Save the changed data by pressing I ENTER I . 
-
41 
-