(Panel Control Parameters) 
Panel 
feedback 
control 
This is used when 
[, 
,-
.F 
b  feedback parameters are used. 
E6580516 
* If no feedback control is selected with the G .-
.F 
b  feedback control selection parameter 
1,c 
b ,o 
:I
, 
feedback control will not occur even if panel feedback control ON (IP F b 
[I 
= O ) is selected. 
•=• 
-
•= •= 
Panel 
reset 
selection 
'  ' 
'-
_, 
The trip causes that can be reset when the inverter trips as a result of a failure or fault, etc., can be selected. 
P.-ES 
setting value  Function 
,-, 
All possible 
w 
I 
Only OL can be reset 
, 
2 
Only OL, OC1, OC2 and OC3 can be reset 
* The trip cause must be removed before the inverter 
is 
reset, or the inverter will trip again. 
OL indicates  0 L  : 
,-, 
, 0 L n c , and  0 L ,- . Resetting 
is 
not possible during the required 
cooling time after tripping. The inverter can be reset, however, by turning the control power OFF. 
Required cooling time under standard settings  O L  : 
,-, 
: Approx. 1 min. 
0 L n c  : Approx. 5 min. 
0 L ,- : Approx. 30 sec. 
- 58 -