E6580516 
7.3.4 JOG Run Mode 
This mode is used to run the inverter at low speeds, and especially allows short-time runs (inching) to 
be done easily. The following explanation is for executing jog from the 
panel. When using terminal block 
signals to execute jog, refer to the parameter explanation section for 
[,,-.SF 
I._: 
O C 
1-
This mode is entered via the following procedure. 
The 
JOG run frequency ( 
k,: 
O 
GI 
in 
[,,-.SF 
) and JOG stop control ( IJ S 
l:: 
PI 
in 
G ,- . 
SF 
) 
parameters must be set from settings monitor mode before entering this mode. (Refer to page 
75. 
) 
Key operation  Example display 
Explanation 
(PRG) 
.,-
, , 
Press the I PRG I key twice. The JOG mode will not be entered 
•U•-·U 
if a different key sequence is pressed. 
(PRG) 
:FJOG 
The JOG mode will be entered when the I PRG I key 
is 
pressed 
the second time only if panel 
control mode 
is 
selected and the 
JOG run frequency setting value 
is 
not 
OHz. 
(Forward JOG) 
If panel 
control mode is not selected or the JOG run frequency 
is 
not set, operation will return to standard monitor mode 
(frequency 
display) when the I PRG I key is pressed the second 
time. 
(2) 
. 
,,-,,-
Execute reverse JOG by pressing "V. 
•l-UC-.IU 
Execute forward JOG by pressing 
.6.. 
B 
s.o 
The JOG run frequency will continue to be output while the 
I RUN I key is held down. 
(PRG) 
,-,  ,-, 
Standard monitor mode will be returned to when I PRG I is 
'-'•'-' 
pressed. 
Note) 
If positioning is attempted 
in 
JOG run mode and the motor shaft does not smoothly stop at the 
desired location, set the output short-circuit detection selection ( 
IO 
CL 
SI 
in 
[, 
,-
.F' ,- ) setting 
value to 
2  {position sensing during JOG). (Refer to page 85. ) 
- 44  -