E6580516 
62 
Terminal Functions 
Table 6.2.1: 
Main 
circuit terminal functions for 
3.7k.W 
and 
smaller units 
Main circuit terminal functions for 3.7kW and smaller units are as shown below. The internal circuit 
diagrams for each terminal are shown 
on 
page 21. 
Internal 
Terminal symbol 
Terminal function 
circuit 
diagram 
G/E 
Terminal for external grounding. 
A 
R/L 1, 
S/L2, T/L3 
Connect to properly-rated power source. 
A 
U/T1, V/T2, W/T3 
Connect to motor(3-phase induction motor). 
B 
PA,PB 
When built-in braking resistor is insufficient, connect 
to 
external braking 
C1 
resistor( optional). 
Change the settings related to dynamic braking resistor protection. 
Note) Do not short-circuit 
PA terminal and PB terminal. 
PC 
Minus potential terminal for internal DC circuit. 
C1 
A DC power source can be input between this terminal and the PA 
terminal (plus potential). 
RO
,
SO 
Control circuit power is input via the shorting bars on the terminal block 
D I 
(R/L 
1-RO
, S/L2-SO). When using a separate 
power 
supply for the control 
power, remove the shorting bars before connecting the power supply. 
(PR1 
), 
(PB1) 
Connected to the 
built-in braking resistor. 
When 
not using the built-in 
C1 
braking resistor, change the wiring from(PB1 )to(PR1 
), 
and then 
change the settings of the dynamic braking resistor operation 
parameters. 
(PA1) 
This is an 
internal connection, 
so 
do 
not remove wires from if or 
C1 
connect external wires 
to 
it.  It is connected to the built-in braking 
resistor. 
(E) 
This is for internal connections, 
so 
do 
not remove or connect external 
A 
wires. This is wired to the inverter chassis. 
Table 
6.2.2: 
Main 
circuit terminal functions 
for 
5.SkW 
and 
larger units 
Main circuit terminal functions for 5.5kW and larger units are as shown below. The internal circuit 
diagrams for each 
terminal are shown 
on 
page 
21
. 
Internal 
Terminal symbol 
Terminal function 
circuit 
diagram 
G/E 
Terminal for external qrounding. 
A 
R/L, 
S/L2,  T/L3 
Connect to 
properly-rated power source. 
A 
U/T1, V/T2, W/T3  Connector to motor(3-phase induction motor). 
B 
PA. PB 
Connect to braking resistor(optional)and then set the dynamic 
C2,C3,C4 
braking resistor operation parameters. 
Note) Do not short-circuit 
PA terminal and PB terminal. 
PC 
Minus potential terminal for internal DC main circuit. 
C2,C3,C4 
A DC power source can be input between this 
terminal and the PA 
terminal(plus 
potential). 
PO, 
PA  Terminals for connecting a DC-link reactor(DCL)(standalone type). 
C2,C3,C4 
This is short circuited with s shorting bar at shipment. 
RO,SO  Control circuit power 
is 
input via the shorting bars on the main circuit 
D1
.D2 
terminal block(RO-R/L 1,SO-S/L2). When using a separate power supply 
for control power, remove the shorting bars before connecting the 
power 
supply. 
On 
37kW and larger units, these terminals are not connected to the 
main circuit 
terminals at shipment, so connect a power supply for the 
control circuit. 
R20,S20 
Power supply output terminals(190 to 220V-50Hz, 190to 
230V-
02 
60Hz)for operation circuits. Only inst
al
led on  400V-class 37kW 
and 
larqer units(10VA). 
- 18  -
I 
I 
I