Open collector output detection level 
Setting 
Function 
value 
I '-I 
Overcurrent pre-alarm 
Output terminal selections ® 
"ON"  : open collector transistor ON 
"OFF" 
: open collector transistor OFF 
Detection level 
"ON" 
during overcurrent stall protection operation 
E6580516 
"ON" when the output current reaches the setting value level of 
StL 
, .  r  o 
5'-'2
'  r 
c-=i 
, 
1n 
'-''-
., 
,-
, or 
c;;; 
,_ 
m 
'-''-
.,  c 
when using fundamental parameters #2. 
(Same level as the blinking  [  alarm on the operating panel 
LED) 
:s 
Inverter overload pre-alarm  "ON" when the cumulative trip amount of  O L 
I,-, 
(inverter 
overload trip} 
is 
50% or more of the trip level. 
:s 
Motor overload pre-alarm 
"ON" 
when the cumulative trip amount or  O L n t  (motor 
overload trip} is 50% or more of the trip level. 
ao 
Overheat pre-alarm 
"ON" 
when heatsink temperature is 
84°C 
or higher 
Once "ON", turns "OFF" again when temperature drops to 
80°C 
or 
less 
c'c' 
Overvoltage pre-alarm  "ON" during overvoltage limit operation (OP stall} of 
DC 
main 
circuit 
voltage. 
200V 
system: approx. 370Vdc 
400V 
system: approx. 7 40Vdc 
(Same level 
as the blinking  P  alarm on the operating panel 
LED) 
c''-: 
Undervoltage alarm  "ON" when main circuit DC voltage is below the following levels: 
200V 
system: approx. 200Vdc 
400V 
system: approx. 380Vdc 
c'6 
Undercurrent alarm  "ON" when output current 
is 
lower than the setting value of 
L L 
,0 
[  in 
[, 
,-
. P ,- and continues for longer than the 
time set 
in 
LL 
F't 
c'B 
Overtorque alarm 
"ON" 
when the toque current exceeds the setting value of 
Gt 
L 
in 
[,,-
.F',-
30 
Braking resistor overload 
"ON" 
when the 
[IL 
,-
cumulative trip amount 
is 
50% or more 
pre-alarm  of the trip level. 
*The 
checking conditions for the following alarm outputs differ from each other as indicated: 
Undervoltage alarm : Checked while running. 
Undercurrent 
alarm  : Checked during run command. 
Overtorque 
alarm  : Constantly checked. 
Note) During reset, 
all status alarms will enter the OFF state regardless of the operating conditions. 
-
63 
-