Braking during power off: 
Loads that generate a 
negative torque: 
Motors with brakes: 
3-phase power source 
(a) 
E6580516 
The inverter will enter the coast-stop state when the power source is 
turned off. The motor 
will therefore not stop immediately. 
To 
stop the 
motor 
immediately, install an auxiliary brake unit. Dynamic braking 
units and mechanical braking units are 
available, so select one that 
suits your specific 
application. 
The overvoltage protection 
or 
overcurrent protection may function and 
trip the inverter when used with 
loads that generate a negative torque. 
In this case, a braking resistor that meets the load condition must be 
installed. 
If 
a motor with a brake is directly connected to the inverter, the 
voltage when the motor is started 
will be low, which may result 
in 
the 
brake not being 
released. In this case, separately wire the brake 
circuit and motor main circuit. 
In 
addition, there is a delay 
in 
the time 
to when the inverter output stops if the inverter's 
ST to CC control 
terminal 
connection is released, so use of the circuit configuration 
in 
Fig. 
4-1 
is recommended. 
In 
Fig. (a), the brake power is turned ON and OFF via MC2 and MC3. 
If a circuit configuration as shown 
in 
the drawing is not used, a bound 
current may 
flow during braking and may cause an overcurrent trip. 
The brake power can 
also be turned ON and OFF using the low-
speed signal LOW as shown 
in 
Fig. (b). 
(Non-excited brake) 
MC2 
MC3 
MC1 
--0 
3-phase power source 
(b) 
Fig. 
4.1 
Circuit configuration for motor with brake 
MC2 
LOW 
LOW~C3 
MC3 
MC2 
In some cases, such as 
in 
hoist applications, turning the brake ON  and 
OFF by using low-speed detection (LOW terminal function) may be better, 
so contact your 
dealer for further details. 
4.2 Cautions Regarding the Inverter 
Inverter's 
overcurrent 
protection: 
Overcurrent protection 
is 
used as the VF-AS inverter's protection 
function, and the current setting 
level 
is 
set to match the largest 
applicable 
motor. Therefore. when operating a motor that 
is 
smaller 
than the inverter capacity, the overcurrent level and electronic thermal 
protection parameters must be readjusted. (Refer to pages 77, 
78.) 
- 6  -