EasyManuals Logo

Toshiba Tosvert VF-S15 User Manual

Toshiba Tosvert VF-S15
394 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #134 background imageLoading...
Page #134 background image
E6582175
F-22
6
1) Simultaneous setting of vector control and auto-tuning (f400=2)
Set the basic parameter  (Torque boost setting macro function) to
Refer to section 6.1.5 for details.
2) Automatic setting
Set the extended parameter  (auto-tuning) to . Refer to section 6.25 selection 2 for details.
3) Manual setting
Set each motor constant. Refer to section 6.25 selection 4 for details.
5) Energy-saving
Setting of V/F control mode selection  to (Energy-saving)
Energy can be saved in all speed areas by detecting load current and flowing the optimum current that fits
the load.
If the motor you are using is a 4P Toshiba standard motor which has the same capacity as the inverter, there
is basically no need to set the motor constant. There are three setting methods as mentioned below. In any
method, set the following parameters according to the motor’s name plate.
 (Base frequency 1),  (Base frequency voltage 1),  (Motor rated capacity),  (Motor
rated current),  (Motor rated speed)
1) Simultaneous setting of energy-saving and auto-tuning (f400=2)
Set the basic parameter  (Torque boost setting macro function) to 
Refer to section 6.1.5 for details.
2) Automatic setting
Set the extended parameter  (auto-tuning) to . Refer to section 6.25 selection 2 for details.
3) Manual setting
Set each motor constant. Refer to section 6. 25 selection 4 for details.
6) Achieving further energy savings
Setting of V/F control mode selection  to (Dynamic energy-saving)
More substantial energy savings than those provided by setting  to can be achieved in any speed
range by keeping track of the load current and passing a current appropriate to the load. The inverter cannot
respond to rapid load fluctuations, so that this feature should be used only for loads, such as fans and pumps,
that are free of violent load fluctuations.
Motor constant must be set
If the motor you are using is a 4P Toshiba standard motor which has the same capacity as the inverter, there
is basically no need to set the motor constant. There are two setting methods as mentioned below. In any
method, set the following parameters according to the motor’s name plate.
 (Base frequency 1),  (Base frequency voltage 1),  (Motor rated capacity),  (Motor
rated current),  (Motor rated speed)
1) Automatic setting
Set the extended parameter  (auto-tuning) to . Refer to section 6.25 selection 2 for details.
2) Manual setting
Set each motor constant. Refer to section 6.25 selection 4 for details.

Table of Contents

Other manuals for Toshiba Tosvert VF-S15

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba Tosvert VF-S15 and is the answer not in the manual?

Toshiba Tosvert VF-S15 Specifications

General IconGeneral
CategoryInverter
Control MethodV/f control, Sensorless vector control
Cooling MethodForced air cooling
ModelTosvert VF-S15
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat
Communication OptionsModbus RTU
Overload Capacity150% for 1 minute
Braking UnitBuilt-in braking transistor
Output Voltage3-Phase, same as input voltage
Operating Temperature-10 to +50°C (14 to 122°F)
Storage Temperature-20 to 65°C (-4 to 149°F)
Humidity5 to 95% RH (non-condensing)
AltitudeUp to 1000m above sea level
Input Voltage3-Phase 200 to 240 VAC, 3-Phase 380 to 480 VAC
WeightVaries depending on model (e.g., 0.8 kg to 16 kg)

Related product manuals