E6582175
F-63
6
6.19 Trip-less intensification
6.19.1 Auto-restart (Restart of coasting motor)
f301 : Auto-restart control selection
Refer to section 5.9 for details.
6.19.2
Regenerative power ride-through control/Deceleration stop
during power failure/Synchronized acceleration/deceleration
f302 : Regenerative power ride-through control (Deceleration stop)
f317 : Synchronized deceleration time
f318 : Synchronized acceleration time
Function
1) Regenerative power ride-through control:
When momentary power failure occurs during operation, this function makes operation continue using
the regeneration energy from a motor.
2) Deceleration stop during power failure:
When momentary power failure occurs during operation, this function stops the motor quickly and
compulsorily using the regeneration energy from the motor.
Deceleration time varies according to the load.
When the function of the deceleration stop during power failure operates,
the message “” is displayed on the operation panel.
After the forced stop, the inverter remains static until you put off the operation command
momentarily.
3) Synchronized acceleration/deceleration:
When the inverter is used with textile machines, this function decelerate the motors synchronously to
stop in the event of a momentary power failure and accelerate them to reach the targeted frequency
commands synchronously at the recovery from the power failure in order to prevent thread breakage.

Table of Contents

Other manuals for Toshiba Tosvert VF-S15

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba Tosvert VF-S15 and is the answer not in the manual?

Toshiba Tosvert VF-S15 Specifications

General IconGeneral
CategoryInverter
Control MethodV/f control, Sensorless vector control
Cooling MethodForced air cooling
ModelTosvert VF-S15
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat
Communication OptionsModbus RTU
Overload Capacity150% for 1 minute
Braking UnitBuilt-in braking transistor
Output Voltage3-Phase, same as input voltage
Operating Temperature-10 to +50°C (14 to 122°F)
Storage Temperature-20 to 65°C (-4 to 149°F)
Humidity5 to 95% RH (non-condensing)
AltitudeUp to 1000m above sea level
Input Voltage3-Phase 200 to 240 VAC, 3-Phase 380 to 480 VAC
WeightVaries depending on model (e.g., 0.8 kg to 16 kg)

Related product manuals