E6582175
F-147
6
Title Function Adjustment range Default setting
f910
Step-out detection current level 1 - 150 (%) 100
f911
Step-out detection time
0.00: No detection
0.01
-2.55 (s)
0.00
f912
q-axis inductance
0.01-650.0 (mH) 10.00
f913
d-axis inductance
0.01-650.0 (mH) 10.00

Factory specific coefficient 9L
--
Refer to section 6.25.2 about setting motor constants.
Note 1: When using an PM motor, consult your Toshiba distributor, since the inverter is not compatible with all
types of PM motors.
Note 2: The inverter may fail to detect step-out in some cases, because it uses an electrical method to detect
step-out. To avoid detection failures, you are recommended to install a mechanical step-out detector.
6.40 Traverse function
f980 : Traverse selection
f981 : Traverse acceleration time
f982 : Traverse deceleration time
f983 : Traverse step
f984 : Traverse jump step
Refer to “Traverse control Instruction Manual : E6581877” for details.