E6582175
F-29
6
6.6 Input signal selection
6.6.1 Priority selection (Both F and R are ON)
f105 : Priority selection (Both F and R are ON)
Function
This parameter allows you to select the direction in which the motor runs when a forward run (F)
command and a reverse run (R) command are entered simultaneously.
1) Reverse
2) Deceleration stop
[Parameter setting]
Title Function Adjustment range Default setting
f105
Priority selection
(Both F and R are ON)
0: Reverse
1: Deceleration stop
1
(1) [f105 = 0 (Reverse)]: If an F command and an R command are entered simultaneously,
the motor will run in the reverse direction.
Output frequency [Hz]
Forward run
Reverse run
Forward run command
Reverse run command
ON
OFF
ON
OFF
0
Setting frequency
Setting frequency
Time [s]

Table of Contents

Other manuals for Toshiba Tosvert VF-S15

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba Tosvert VF-S15 and is the answer not in the manual?

Toshiba Tosvert VF-S15 Specifications

General IconGeneral
CategoryInverter
Control MethodV/f control, Sensorless vector control
Cooling MethodForced air cooling
ModelTosvert VF-S15
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat
Communication OptionsModbus RTU
Overload Capacity150% for 1 minute
Braking UnitBuilt-in braking transistor
Output Voltage3-Phase, same as input voltage
Operating Temperature-10 to +50°C (14 to 122°F)
Storage Temperature-20 to 65°C (-4 to 149°F)
Humidity5 to 95% RH (non-condensing)
AltitudeUp to 1000m above sea level
Input Voltage3-Phase 200 to 240 VAC, 3-Phase 380 to 480 VAC
WeightVaries depending on model (e.g., 0.8 kg to 16 kg)

Related product manuals