E6582175
F-117
6
6.29.17 Number of starting alarm
f648 : Number of starting alarm
Function
Counting the number of starting, when it will reach the value of parameter
f648 setting, it will be
displayed and alarm signal is output.
[Parameter setting]
Title Function Adjustment range Default setting
f648 Number of starting alarm 0.0-999.0 (10000 times)
999.0
● “0.1” displayed on the monitor refers to 1000 times, and therefore "1.0" denotes 10000 times.
Ex.: 38.5 displayed on the monitor = 385000 (times)
● Display of number of starting alarm information
Number of starting alarm information in the Status monitor mode allows you to check on the time of
replacement. (Refer to chapter 8)
An example of display:

● Output of number of starting alarm signal
The number of starting alarm is assigned to the output terminal.
Setup example) When the number of starting alarm is assigned to the OUT terminal
Title Function Adjustment range Setting
f131 Output terminal selection 2A (OUT) 0-255
162: NSA (Number of
starting alarm)
Setting value 163 is reverse signal.
● The number of starting, forward number of starting and reverse number of starting until present time can be
monitored by setting status monitor mode. (Refer to chapter 8)
● The monitor value of the number of starting, number of forward run and number of reverse run are reset to
0 (zero) by setting
typ=12 (number of starting clear). (Refer to section 4.3.2)

Table of Contents

Other manuals for Toshiba Tosvert VF-S15

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba Tosvert VF-S15 and is the answer not in the manual?

Toshiba Tosvert VF-S15 Specifications

General IconGeneral
CategoryInverter
Control MethodV/f control, Sensorless vector control
Cooling MethodForced air cooling
ModelTosvert VF-S15
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat
Communication OptionsModbus RTU
Overload Capacity150% for 1 minute
Braking UnitBuilt-in braking transistor
Output Voltage3-Phase, same as input voltage
Operating Temperature-10 to +50°C (14 to 122°F)
Storage Temperature-20 to 65°C (-4 to 149°F)
Humidity5 to 95% RH (non-condensing)
AltitudeUp to 1000m above sea level
Input Voltage3-Phase 200 to 240 VAC, 3-Phase 380 to 480 VAC
WeightVaries depending on model (e.g., 0.8 kg to 16 kg)

Related product manuals