Title
Communication
No.
Function Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
0590 Shock monitoring - - 0: Disabled
1: Current detection
2: Torque detection
3: -
0 6.28
0591 Shock monitoring
trip/alarm
selection
- -
0: Alarm only
1: Tripping
0
0592 Shock monitoring
detection direction
selection
- - 0: Over-current / torque detection
1: Low-current / torque detection
0
0593 Shock monitoring
detection level
% 1/0.01 0-250 150
0595 Shock monitoring
detection time
s 0.1/0.1 0.0-10.0 0.5
0596 Shock monitoring
detection
hysteresis
% 1/0.01 0-100 10
0597 Shock monitoring
detection start
waiting time
s 0.1/0.1 0.0-300.0 0.0
0598 Shock monitoring
detection action
selection
- - 0: During operation
1: During operation (except
acceleration / deceleration)
0
0599 Factory specific
coefficient 5A
- - - - * 3
*3: Factory specific coefficient parameters are manufacturer setting parameters. Do not change the value of these parameters.