E6582175
K-30
11
Communication parameters
Title
Communication
No.
Function Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference

0800
Baud rate - - 3: 9600bps
4: 19200bps
5: 38400bps
4 6.38.1

0801
Parity - - 0: No parity
1: Even parity
2: Odd parity
1

0802
Inverter number - 1/1 0-247 0

0803
Communication
time-out time
s 0.1/0.1 0.0: Disabled,
0.1-100.0
0.0

0804
Communication
time-out action
- - 0: Alarm only
1: Trip (Coast stop)
2: Trip (Deceleration stop)
0

0805
Communication
waiting time
s 0.01/0.01 0.00-2.00 0.00

0806
Setting of master
and slave for
communication
between inverters
- - 0: Slave (0 Hz command issued in
case the master inverter fails)
1: Slave (Operation continued in case
the master inverter fails)
2: Slave (Emergency stop tripping in
case the master inverter fails)
3: Master (transmission of frequency
commands)
4: Master (transmission of output
frequency signals)
0

0808
Communication
time-out detection
condition
- - 0: Valid at any time
1: Communication selection of
fmod or cmod
2: 1 + during operation
1

0810
Communication
command point
selection
- 1/1 0: Disabled
1: Enabled
0 6.10.2
6.38.1

0811
Communication
command point 1
setting
% 1/1 0-100 0

0812
Communication
command point 1
frequency
Hz 0.1/0.01 0.0- 0.0

0813
Communication
command point 2
setting
% 1/1 0-100 100

0814
Communication
command point 2
frequency
Hz 0.1/0.01 0.0- *1