E6582175
Q-9
17
Terminal
symbol
Input /
output
Function
Electrical
specifications
FM Output
Multifunction programmable analog output. Default setting: output
frequency.
The function can be changed to meter option (0-1mA), 0-10Vdc voltage
or 0-20mAdc (4-20mA) current output by parameter f681 setting.
Resolution Max. 1/1000.
1mAdc full-scale
ammeter or
QS60T(option)
0-20mA (4-20mA)
DC ammeter
Permissible load
resistance:
600 or less
0-10V DC volt
meter
Permissible load
resistance:
1k or more
P24
Output
24Vdc power output, by changing SW1 to SINK or SOURCE side.
24Vdc-100mA
Input
This terminal can be used as a common terminal when an external
power supply is used by changing SW1 to PLC side.
-
+SU
Input
DC power input terminal for operating the control circuit. Connect a
control power backup device (option or 24Vdc power supply) between
+SU and CC.
Voltage:
24Vdc±10%
Current:
1A or more
Output
It is used with STO for safety function.
+SU and STO terminals are short-circuited by metal bar and the inverter
is put into a standby state at default setting. When the circuit between
them is opened, the motor is coasting stop.
-
STO
Note 2)
Input
When +SU and STO are short-circuited, the inverter is put into a standby
state. (Default setting) And when the circuit between them is opened, the
motor is coasting stop. These terminals can be used for inter lock.
This terminal is not a multifunction programmable input terminal.
It is a terminal with the safety function that complies with SIL II of the
safety standard IEC61508.
Independently of
SW1
ON: DC17V
or more
OFF: DC12V
or less
(OFF: Coast stop)
OUT
NO
Output
Multifunction programmable open collector output. Default setting detect
and output speed reach signal.
Multifunction output terminals to which two different functions can be
assigned.
The NO terminal is an equipotential terminal. It is isolated from the CC
terminal.
By changing parameter f669 settings, these terminals can also be
used as multifunction programmable pulse train output terminals.
Open collector
output
24Vdc-100mA
To output pulse
trains,
a current of 10mA
or more needs to
be passed.
Pulse frequency
range:
10~2kpps

Table of Contents

Other manuals for Toshiba Tosvert VF-S15

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba Tosvert VF-S15 and is the answer not in the manual?

Toshiba Tosvert VF-S15 Specifications

General IconGeneral
CategoryInverter
Control MethodV/f control, Sensorless vector control
Cooling MethodForced air cooling
ModelTosvert VF-S15
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat
Communication OptionsModbus RTU
Overload Capacity150% for 1 minute
Braking UnitBuilt-in braking transistor
Output Voltage3-Phase, same as input voltage
Operating Temperature-10 to +50°C (14 to 122°F)
Storage Temperature-20 to 65°C (-4 to 149°F)
Humidity5 to 95% RH (non-condensing)
AltitudeUp to 1000m above sea level
Input Voltage3-Phase 200 to 240 VAC, 3-Phase 380 to 480 VAC
WeightVaries depending on model (e.g., 0.8 kg to 16 kg)