E6582175
A-29
1
Mandatory
action
Operate under the environmental conditions prescribed in the instruction manual.
Operations under any other conditions can result in malfunction.
Check to make sure that the input power voltage is +10%, -15% of the rated power voltage (±10%
when the load is 100% in continuous operation) written on the name plate.
If the input power voltage is not +10%, -15% of the rated power voltage (±10% when the load is 100%
in continuous operation), this can result in fire.
Caution
Prohibited
Do not install the inverter in any location subject to large amounts of vibration.
This could cause the unit to fall, resulting in bodily injury.

Table of Contents

Other manuals for Toshiba Tosvert VF-S15

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba Tosvert VF-S15 and is the answer not in the manual?

Toshiba Tosvert VF-S15 Specifications

General IconGeneral
CategoryInverter
Control MethodV/f control, Sensorless vector control
Cooling MethodForced air cooling
ModelTosvert VF-S15
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat
Communication OptionsModbus RTU
Overload Capacity150% for 1 minute
Braking UnitBuilt-in braking transistor
Output Voltage3-Phase, same as input voltage
Operating Temperature-10 to +50°C (14 to 122°F)
Storage Temperature-20 to 65°C (-4 to 149°F)
Humidity5 to 95% RH (non-condensing)
AltitudeUp to 1000m above sea level
Input Voltage3-Phase 200 to 240 VAC, 3-Phase 380 to 480 VAC
WeightVaries depending on model (e.g., 0.8 kg to 16 kg)