The space shown in the diagram is the minimum allowable space. Because air cooled equipment has cooling
fans built in on the top or bottom surfaces, make the space on top and bottom as large as possible to allow
for air passage.
Note: Do not install in any location where there is high humidity or high temperatures and where there are
large amounts of dust, metallic fragments and oil mist.
Calorific values of the inverter and the required ventilation
About 5% of the rated power of the inverter will be lost as a result of conversion from AC to DC or from DC to
AC. In order to suppress the rise in temperature inside the cabinet when this loss becomes heat loss, the
interior of the cabinet must be ventilated and cooled.
The amount of forcible air-cooling ventilation required and the necessary heat discharge surface quantity
when operating in a sealed cabinet according to motor capacity are as follows.
Voltage class Inverter type
Calorific values (W)
Note 1)
Amount of forcible air
cooling ventilation
required (m
3
/min)
Heat discharge
surface area required
for sealed storage
cabinet (m
3
)
Standby
power
requirement
(W)
Note 2)
4kHz 12kHz 4kHz 12kHz 4kHz 12kHz
Three-phase
240V class
VFS15-
2004PM-W1
2007PM-W1
2015PM-W1
2022PM-W1
2037PM-W1
2055PM-W1
2075PM-W1
2110PM-W1
2150PM-W1
35 40
0.20 0.23 0.70 0.80
14
45.6 50
0.26 0.28 0.91 0.99
14
81 92
0.46 0.52 1.61 1.85
16
94.9 104
0.54 0.59 1.90 2.07
16
139 154
0.79 0.87
2.77 3.08 18
256 283
1.45 1.61
5.12 5.66 22
305 367
1.73 2.08
6.10 7.34 22
475 538
2.70 3.05
9.50 10.76 31
557 628
3.16
3.56 11.14 12.56 31
Single-phase
240V class
VFS15S-
2002PL-W1
2004PL-W1
2007PL-W1
2015PL-W1
2022PL-W1
23
37
46
79
101
24.8
42.2
50
90
110
0.13
0.21
0.26
0.45
0.58
0.14
0.24
0.28
0.51
0.62
0.46
0.74
0.92
1.57
2.03
0.50
0.84
1.00
1.80
2.20
14
14
14
16
16
Three-phase
500V class
VFS15-
4004PL-W1
4007PL-W1
4015PL-W1
4022PL-W1
4037PL-W1
4055PL-W1
4075PL-W1
4110PL-W1
4150PL-W1
30 39
0.17 0.22 0.61 0.78
18
39 50
0.22 0.28 0.78 1.00
18
58 76
0.33 0.43 1.15 1.53
18
77 102
0.44 0.58 1.53
2.04 18
131 156
0.75 0.88
2.63
3.12
20
211 263
1.20 1.49
4.22 5.26 22
254 346
1.44 1.96
5.08 6.92 22
387 470
2.20 2.67
7.74 9.40 31
466 572
2.65 3.25
9.32 11.44 31
Note 1) Case of 100% Load Continuation operation. The heat loss for the optional external devices (input AC
reactor, radio noise reduction filters, etc.) is not included in the calorific values in the table
Note 2) It is power consumption when power is on but is not output (0Hz), and cooling fan is activated (model
with cooling fan).

Table of Contents

Other manuals for Toshiba Tosvert VF-S15

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba Tosvert VF-S15 and is the answer not in the manual?

Toshiba Tosvert VF-S15 Specifications

General IconGeneral
CategoryInverter
Control MethodV/f control, Sensorless vector control
Cooling MethodForced air cooling
ModelTosvert VF-S15
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat
Communication OptionsModbus RTU
Overload Capacity150% for 1 minute
Braking UnitBuilt-in braking transistor
Output Voltage3-Phase, same as input voltage
Operating Temperature-10 to +50°C (14 to 122°F)
Storage Temperature-20 to 65°C (-4 to 149°F)
Humidity5 to 95% RH (non-condensing)
AltitudeUp to 1000m above sea level
Input Voltage3-Phase 200 to 240 VAC, 3-Phase 380 to 480 VAC
WeightVaries depending on model (e.g., 0.8 kg to 16 kg)