CVHH-SVX001A-EN 49
Customer-Supplied Remote Starter Wiring
Table 14. Standard customer-supplied remote field wiring requirements
Pow er Supply W iring to Starter Panel
Starter Panel
Terminals
Starter by others 3-Phase power wiring
See starter by others
schematic
Starter to Motor Pow er W iring Starter Motor
Rem ote Starter to Chiller Motor Junction
Box
(a)
T1 through T6 T1 through T6
Pow er Supply W iring t o Unit -M ou nt ed
Control Pow er Transformer ( CPTR)
Control Pow er
Transform er
Terminals
3-Phase Line Voltage
(b)
6Q1-1,3,5
Ground CPTR panel GND
Starter to Control Panel 12 0 Vac
Control W iring
Starter Panel
Terminals
Unit Control Panel
Term inations
Power from control panel 1F1 5X12-3 1X1-2
Neutral from control panel 5X12-2 1X1-13
Ground from control panel 5X12-G 1X1-G
Interlock relay signal 5X12-4 1K23 J10-1
Start contactor signal 5X12-5 1K23 J8-1
Oil Pum p Interlock 5X12-7, 5X12-8 1X1-10, 1X1-21
Run contactor signal 5X12-10 1K23 J6-1
Transition complete 5X12-14 1K23 J12-2
Solid State Starter Fault
(c)
5X12-12
5X12-11
1K13 J2-2
1K13 J2-1
Low Voltage Circuits less than 30 Vac
Starter Panel
Terminals
Unit Control Panel
Term inations
Standard Circuits
Current Transformers (see
Table 15, p. 50)
(Required)
(d)
5X12-19 1K23 J7-1
Note: Phasing must be
maintained
5X12-20 1K23 J7-2
5X12-21 1K23 J7-3
5X12-22 1K23 J7-4
5X12-23 1K23 J7-5
5X12-24 1K23 J7-6
Potential Transformers (Required)
(d)
5X12-25 1K23 J5-1
5X12-26 1K23 J5-2
5X12-27 1K23 J5-3
5X12-28 1K23 J5-4
5X12-29 1K23 J5-5
5X12-30 1K23 J5-6
Notes:
1 . All wiring to be in accordance with National Electrical Code and any local codes.
2 . Refer to ship-with wiring schematics; some terminals may vary based on unit.
(a) For AWG/ MCM equivalents in mm
2
, refer to
Tab le 1 2 , p . 4 7 . Wires, lugs, and fuses/ breakers are sized based on National Electric Code NEC [ NFPA 70]
and UL 1995.
(b) Refer to submittal and ship-with wiring schem atics for voltage requirements.
(c) Solid State Starter Fault input is used with low-and medium-voltage, custom er-supplied solid state starters only.
(d) Must be separated from 120 Vac and higher wiring.