EasyManua.ls Logo

Trane CVHH - Compressor Oil Change; Leak Checking Based on Purge Pump out Time

Trane CVHH
111 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Recommended Maintenance
CVHH-SVX001A-EN 93
Compressor Oil Change
After the first six months of accumulated operation, or
after 1,000 hours operation—whichever comes first—it is
recommended to change the oil filter. It is recommended
to subscribe to the Trane annual oil analysis program
rather than automatically change the oil as part of
scheduled maintenance. Change the oil only if indicated
by the oil analysis. Use of an oil analysis program will
reduce the chiller’s overall lifetime waste oil generation
and minimize refrigerant emissions. The analysis
determines system moisture content, acid level, and wear
metal content; it can be used as a diagnostic tool. Due to
the new refrigerant and oil combination, the oil analysis
should be performed by the Trane Chemical Laboratory.
In conjunction with other diagnostics performed by a
qualified service technician, oil analyses can provide
valuable information on the performance of the chiller to
help minimize operating and maintenance costs and
maximize its operating life. An access valve is installed in
the oil supply line, before the oil filter, for obtaining oil
samples.
Notes:
Use only Trane OIL00022. A full oil change is 79.5 L
(21 gallons).
Leak Checking Based on Purge
Pump Out Time
Figure 52 has been developed to aid in determining when
to do a leak check of a chiller based on the purge pump out
time and unit size. This figure depicts normal purge pump-
out times, small leaks and large leaks based on the chiller
tonnage.
If the purge pump-out time is in the small leak region, then
a leak check should be performed and all leaks repaired at
the earliest convenience. If the purge pump-out time is in
the large leak region, a thorough leak check of the unit
should be performed immediately to find and fix the leaks.
Measu re t h e com p r essor m ot o r w in din g r esi st an ce
to ground; a qualified service technician should
conduct this check to ensure that the findings are
properly interpreted. Contact a qualified service
organization to leak-test the chiller; this
procedure is especially important if the system
requires frequent purging.
(a) Every three years, use a nondestructive tube test to inspect the condenser and evaporator tubes. It may be desirable to perform tube tests on these
com ponents at more frequent intervals, depending upon chiller application. This is especially true of critical process equipment.
(b) Contact a qualified service organization to determ ine when to conduct a complete examination of the unit to discern the condition of the com pressor
and internal components. Check the following: chronic air leaks (which can cause acidic conditions in the compressor oil and result in premature bearing
wear) and evaporator or condenser water tube leaks (water m ixed with the com pressor oil can result in bearing pitting, corrosion, or excessive wear).
Table 20. Recommended maintenance (continued)
Table 21. Recommended maintenance of optional features
Feature Every 3 m onths Every 6 m onths Annually
Waterbox Coatings Inspect waterbox coatings within the
f ir st 1 3 mon t h s t o d et er min e a r equ ir ed
maintenance schedule for your job site.
Refer to
Waterbox and Tubesheet
Protective Coatings,” p. 97 for more
information.
Waterbox Anodes I nspect waterbox anodes wit hin t he first
13 months to determine a required
maintenance schedule for your job site.
Refer to
Sacrificial Anodes,” p. 97 for
more information.
Gantries Lubricate the gantries annually. Use ConocoPhillips
MegaPlex
®
XD3 (gray in color), LPS
®
MultiPlex Multi-
Purpose (blue in color), or equivalent.
Hinges
Lubricate the hinges annually. Use ConocoPhillips
MegaPlex
®
XD3 (gray in color), LPS
®
MultiPlex Multi-
Purpose (blue in color), or equivalent.

Table of Contents

Related product manuals