EasyManua.ls Logo

Ulvac C30HVRT - Section 2 Considerations before Installation; Wiring Requirements; Table 2-1 Input Power Cable Specifications

Default Icon
94 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Section 2. Considerations before Installation
Refer to Figure 1-2 in Section 1 for the dimensions of the compressor.
Figure 2-1 Required space for compressor installation (scale: mm) and
levelness
2.2 Wiring requirements
Table 2-1 shows the specifications of optional input power cables. For connecting
procedures of the input power cable refer to “Section 4.6 Electrical connections”.
Table 2-1 Input power cable specifications
Item Symbol
C30HVRT
Input power cable
INPUT
POWER
Copper wire / 600VAC,
3 conductors with ground
(*1)
5.5mm
2
, 8 mm
2 (*2)
(*1)
The color of the ground wire is green.
(*2)
Unless otherwise specified, 5.5 mm
2
cables
are attached to the compressor.
Supply AC power for compressor from the equipment-side distribution panel. The
distribution panel should have branched circuit breakers for each compressor (see Figure
2-2). Circuit breakers must be appropriate and meet the international and the national
codes and standards of the country installed (Refer to UL489 and IEC60947-2). Also,
circuit breakers must be installed in the distance to be able to check the compressor.
Refer to Table 1-2 in section 1 for circuit breaker current rating.
D > 50
H > 300
Compressor
C30HVRT
D > 50
Wall,
C30HVRT, or
other
e
q
ui
p
ment
Slope <±5degrees
Front view Top view
D>500
Wall,
C30HVRT, or
other
equipment
D>500
D>50
D>50
Front
CAUTION
In most standards, it is required to install a branch breaker to protect power cables connected
to the equipments. A circuit breaker must be installed. Failure to follow this procedure could
seriously damage the equipment.
2-2
ULVAC CRYOGENICS INCORPORATED

Table of Contents