PARAMETER VALUE DESCRIPTION DEFAULT MEMO
StoP
STOP INPUT
no
no
The input STOP is not available (ignored by the control unit)
ProS
The input STOP stops the gate: pressing the command START the gate
continues the motion
invE
The command STOP stops the gate: at the next START the gate starts
moving in the opposite direction
Fot1
Photocell 1 input
This menu allows enabling the input for type 1 photocells, that is to say,
photocells active both during the opening and closing phase
no
no
Input disabled (ignored by the control unit)
AP.Ch
Input enabled
PrES
If the photocells are activated, the gate opens and remains open until
deactivated
Fot2
Photocell 2 input
This menu allows enabling the input for type 2 photocells, that is to say,
photocells non active during the opening phase
CFCh
CFCh
Input enabled even at standstill gate too: the opening movement does not
start if photocell is interrupte
Ch
Input enabled for the closing phase only
WARNING: if you select this option, you must disable photocell test
no
Input disabled (ignored by the control unit)
Ft.tE
Test of the photocells
no
no
Function deactivated
Si
In order to achieve a safer operation for the user, the unit performs a
photocells operational test, before a normal working cycle.
If no operational faults are found, the gate starts moving.
Otherwise, it will stand still and the flashing light will stay onfor 5 sec.
The whole test cycle lasts less than one second.
CoS1
Safety ribbon 1 input
This menu allows enabling the input for type 1 safety ribbon, that is to say,
fixed ribbons
no
no
Input disabled (ignored by the control unit)
AP
Input enabled during the opening and disabled during the closure
APCh
Input enabled in opening and closure
FirE
If the input is activated, the gate opens. To close the gate the input must
be deactivated and a command must be sent to start the maneuver
(automatic closing does not work).
CoS2
Safety ribbon 2 input
This menu allows enabling the input for type 2 safety ribbon, that is to say
mobile ribbons
no
no
Input disabled (ignored by the control unit)
APCh
Input enabled in opening and closure
Ch
Input enabled during closure and disabled during opening