Installation vacon • 59
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
5
6 26.46 23.63 21.46 19.74 18.36 17.22
7 30.86 27.57 25.03 23.03 21.42 20.10
8 35.27 31.51 28.61 26.32 24.48 22.97
9 39.68 35.45 32.19 29.61 27.54 25.84
10 44.09 39.38 35.76 32.90 30.60 28.71
Table 20. Cooling agent flow rates (l/min) in relation to power loss at certain glycol/water mixture
Power loss [kW] Glycol/Water ratio
100/0 80/20 60/40 40/60 20/80 0/100