Electrical cabling and connections vacon • 113
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
6
Figure 59. Terminals and connections between the star-coupler board, ASIC boards and feedback boards
(CH64 and CH74)
NOTE! The minimum optical cable bending radius is 50 mm.
NOTE! Terminals X2 and X3 can be in use simultaneously. However, if the +24 V supply from the
control I/O terminals (e.g. from board OPT-A1) is used, this terminal must be protected with a diode.
Fix the cable bundle at two or more points, at least one at each end, to prevent damages to the
cables.
Fasten the removed cover(s) on the inverter module when the work is finished.
6.3.3 Connections between mains device and inverter power module
The dimensions in the table below must be taken into account if some kind of mains device (e.g.
fuse, switch fuse, contactor) is used in the input line between the mains and the VACON
®
Liquid-
Cooled inverter.
Be careful when connecting the fibre optic cables! Connecting the wires
incorrectly may damage power electronic components.
nxw13.fh11
Star coupler board on control unit
H18 Trip signal from power module 2
H17 VaconBus data from ASIC 2 to control board
H16 VaconBus data from control board to ASIC 2
H15 ADC synchronization, power module 2
H14 Phase W control, power module 2
H13 Phase V control, power module 2
H12 Phase U control, power modu le 2
H11 Gate control enable, power module 2
H23
Feedback phase W
H22
Feedback phase V
H21
Feedback phase U
Terminals on ASIC board of power module 1
H1 Gate control enable
H2 Phase U control
H3 Phase V control
H4 Phase W control
H5 ADC synchronization
H6 VaconBus data from control board to ASIC
H7 VaconBus data from ASIC to control board
Terminals on ASIC board of power module 2
H8 Trip signal from power module 1
H7 VaconBus data from ASIC 1 to control board
H6 VaconBus data from control board to ASIC 1
H5 ADC synchronization, power module 1
H4 Phase W control, power module 1
H3 Phase V control, power module 1
H2 Phase U control, power module 1
H1 Gate control enable, power module 1
H10 Trip signal
Terminals on FB board of power module 2
H1 Gate control enable
H2 Phase U control
H3 Phase V control
H4 Phase W control
H5 ADC synchronization
H6 VaconBus data from control board to ASIC
H7 VaconBus data from ASIC to control board
H10 Trip signal
H11 Feedback phase U
H12 Feedback phase V
H13 Feedback phase W
Terminals on FB board of power module 1
H12
H13
H14
H15
H16
H17
H18
H11
H23
H22
H21
H2
H3
H4
H5
H6
H7
H8
H1
H10 FB PM1
H7 ASIC PM1
H6 ASIC PM1
H5 ASIC PM1
H2 ASIC PM1
H3 ASIC PM1
H4 ASIC PM1
H1 ASIC PM1
H10 FB PM2
H7 ASIC PM2
H6 ASIC PM2
H5 ASIC PM2
H4 ASIC PM2
H3 ASIC PM2
H2 ASIC PM2
H1 ASIC PM2
H13 FB PM1
H12 FB PM1
H11 FB PM1
Explanations of abbreviations:
A SIC = A SIC boa rd
FB = Feedback board
PM1 = Power Module 1
PM2 = Power Module 2
11373_uk