3.2.1 Compliance with EN50131 Approvals
Software Requirements
l In the Standards settings page, select Europe under Region to implement EN50131
requirements.
l Select Grade 2 or Grade 3 to implement the grade of EN50131 compliance.
l The Wireless setting Prevent Setting Time must be set to a value greater than 0 and less than
20.
l The Wireless setting Device Lost Time must be set to a value less than 120.
l The X-BUS Settings, Retries, must be set to a value of 10.
l The X-BUS Settings, Comms timer, must be set to a value of 5.
l Select Synchronization Time with Mains under Clock settings to use mains as clock master.
SPC4xxx/5xxx/6xxx – Installation & Configuration Manual Directives and standards