Restriction
System
Option
Description
End Of Line
(EOL
RESISTANCE)
Select the End Of Line termination resistors that will apply to either all zones on
the system or new zones added to the system. Select a value to enable the
appropriate feature.
To apply a new EOL setting to all existing zones, select the Update all zones
checkbox. If you change the End of Line value but do not select this checkbox,
the new setting applies only to zones added after changing the value.
EOL Wide If enabled, EOL wide bands are used.
Suspicion
Audible
If enabled then WPA* Suspicion alerts have audible and visible indicators on
the keypad (Financial mode only).
Seismic Test
on Set
If enabled, all seismic sensors in any area that is being set will be tested before
area or system set (Financial mode only).
Auto Restore Enable this feature to automatically restore alerts on the system, that is, when
the open zone that triggered an alarm is closed, a manual restore operation on
the keypad/browser is not required. If disabled it prevents the user from
restoring alerts by resetting the input that triggered the alert.
Alarm on Exit Enabled: If a non-entry/exit zone is activated during the exit timer countdown,
a local alarm is raised by sounding the bells.
Disabled: If a non-entry/exit zone is activated during the exit timer countdown,
an alarm is not raised.
Note: This option only displays when the Unrestricted grade is selected as
enabling it is not in accordance with EN50131. When you choose the Swiss or
Belgium Region under Standard Compliance Settings, this option is
automatically enabled but it is not visible under Options.
Alarm on Entry Enabled: If a non-entry/exit zone is activated during the entry timer
countdown, a local alarm is raised by sounding the bells.
Disabled: If a non-entry/exit zone is activated during the entry timer
countdown, an alarm is not raised.
Note: This option only displays when the Unrestricted grade is selected as
enabling it is not in accordance with EN50131. When you choose the Swiss
Region under Standard Compliance Settings, this option is automatically
enabled but it is not visible under Options.
Confirmation
Confirmation The Confirmation variable determines when an alarm is deemed to be a
confirmed alarm.
l BS8243:
This will enforce compliance with the UK Police requirements, and is a
specific requirement for UK Commercial installations. The requirement
stipulates that an alarm will only be deemed to be a confirmed alarm if it
meets the following condition:
After an initial zone alarm has been activated and before the alarm
confirmation time has expired, a second zone alarm is activated. The
alarm confirmation time must be between 30 and 60 minutes. (See Timers
on page261.)
SPC4xxx/5xxx/6xxx – Installation & Configuration Manual Engineer programming via the browser
© Vanderbilt 2018 256 A6V10276959-d