Open-circuit Applications
The cooling unit receives cooling water in an open circuit from an external cooling water source. For open-
circuit applications note the following:
Use the unit with mains or well water. Do not use water from an evaporative cooling tower
unless the water hardness is controlled.
The water pressure must be 29to145psi (2to10 bar). If water pressure is outside this range,
contact Vertiv for technical support.
The required water flow at different temperatures is available from Vertiv technical support.
If water temperature is very low, insulate both pipes.
Closed-circuit Applications
The cooling unit receives cooling water in a closed circuit using a drycooler. For closed-circuit
applications, note the following:
Install a pump system calculated on the basis of the flow and total head of the system (see site
plan data) and controlled by the compressor running (see label on the unit).
Insulate both pipes.
IMPORTANT! Add water and ethylene glycol to the circuit when the ambient temperature is below 32°F
(0°C). Refer to the Liebert CRV System Design Manual, SL-11978). Do not exceed the nominal operating
pressure of the circuit components.
Bleed air out of the circuit.
The following figure shows the recommended installation of a drycooler.
Vertiv | Liebert CRV Installer/User Guide | 54