Liebert® SRC-G
User Manual
Precision Air Conditioning

Table of Contents

Questions and Answers

  • H
    hhallSep 7, 2025
    What causes power supply over-voltage alarm in Vertiv Liebert SRC-G Air Conditioner?
    • K
      Karen TorresSep 8, 2025
      A power supply over-voltage alarm in your Vertiv Air Conditioner indicates that the power supply voltage deviates from the set value. Check if the power input line voltage is in good condition.
  • J
    johnsonstephanieAug 22, 2025
    What to do if Vertiv Liebert SRC-G has no cooling?
    • N
      Nicole MathewsAug 22, 2025
      If your Vertiv Air Conditioner isn't cooling, several factors could be the cause. First, check if the compressor contactor is engaging. If it is not, check for 220 Vdc of coil. If the voltage is correct, verify the contactor is properly connected. Also, a high compressor discharge pressure could be the problem, so check for a 'High pressure alarm' and follow the maintenance steps. A plugged strainer might also be the culprit; inspect it for clogs or damage, and clean or replace it as needed. Finally, a low refrigerant charge could be the issue. Use a suction and discharge pressure gauge to check if the pressure meets the requirement, and look for bubbles in the sight glass.
  • L
    lmillsSep 5, 2025
    What triggers high humidity alarm on Vertiv Air Conditioner?
    • H
      Heather BrightSep 5, 2025
      A high humidity alarm on your Vertiv Air Conditioner can be triggered if the high humidity setpoint is unreasonable, so try resetting the setpoint. Another potential cause is if a vapor barrier is not installed in the room; check for the vapor barrier.
  • T
    Tina FisherSep 3, 2025
    What causes no display and unresponsive buttons but normal operation on Vertiv Liebert SRC-G Air Conditioner?
    • M
      mcmahonnormaSep 3, 2025
      If your Vertiv Air Conditioner has no display and the control buttons do not respond, but the unit operates normally, the issue might be a disconnection between the keypad and control board. Check if the connections between the keypad and control board are firmly connected.
  • B
    Bobby WebbSep 2, 2025
    What to do when Vertiv Liebert SRC-G Air Conditioner shows a power loss alarm?
    • A
      Adam LopezSep 2, 2025
      If your Vertiv Air Conditioner displays a power loss alarm, especially after the unit was in operation and power was lost and then restored, check if the power input line is in good condition.
  • L
    Lauren MorganAug 31, 2025
    Why is there a high temperature alarm on my Vertiv Liebert SRC-G?
    • L
      Linda KramerAug 31, 2025
      A high temperature alarm on your Vertiv Air Conditioner may occur if the high temperature setpoint is unreasonable; try resetting the setpoint. Also, the room load exceeding the unit's design ability can trigger this alarm, so check for room sealing issues or consider capacity expansion.
  • J
    jennaevansAug 30, 2025
    What does SPD alarm mean on Vertiv Liebert SRC-G?
    • A
      alexander74Aug 30, 2025
      An SPD alarm on your Vertiv Air Conditioner indicates a potential issue with the Surge Protection Device. This could be due to SPD failure, in which case you should replace the SPD switch. It could also be due to low supply power voltage, so check for power supply voltage at the SPD, if available.
  • R
    Robert PowersAug 29, 2025
    How to troubleshoot abnormal display on Vertiv Air Conditioner?
    • W
      weekssheriAug 29, 2025
      If your Vertiv Air Conditioner's display is abnormal, it could be due to static discharge. Try disconnecting the system power supply and then restarting it. Another potential cause is a loose connection between the keypad and control board. After powering off the unit, check that the connections are firmly fixed, and then restart the unit.
  • D
    Darrell MccoyAug 27, 2025
    What causes low pressure alarm on Vertiv Liebert SRC-G?
    • H
      Holly GreeneAug 27, 2025
      A low pressure alarm on your Vertiv Air Conditioner can be triggered by a few things. One potential cause is refrigerant leakage; check for any leaking points, fix them immediately, and then recharge the system with an adequate amount of refrigerant. Another possible cause is low outdoor ambient temperature. Also check if the outdoor unit cabling is correct; and check whether the condensate pressure sensor works normally.
  • T
    Terry AndersonAug 27, 2025
    What to do if Vertiv Liebert SRC-G Air Conditioner has no display, control buttons do not respond and unit has no output?
    • J
      Jill WattsAug 27, 2025
      If your Vertiv Air Conditioner shows no display, the control buttons are unresponsive, and the unit has no output, begin by checking for low power supply voltage. Also check if the connections between the control board and control board are firmly connected.

Summary

Document Overview and Styling

Purpose of the Document

Explains the purpose and scope of the user manual for the Liebert SRC-G unit.

Styling Used in this Guide

Defines the visual styles used in the manual for warnings, cautions, and notes.

Version History

Records the revision history and changes made to the document.

Safety Precautions and Measures

Key Safety Guidelines

Details critical safety precautions and measures to be followed during installation and maintenance.

Chapter 1: Overview

1.1. Product Introduction

Introduces the Liebert SRC-G as a wall-mounted precision air conditioner for equipment rooms.

1.2. Model Description

Explains the 18-digit nomenclature used to define Vertiv Liebert SRC-G series models.

1.4. Main Components

Describes the key components of the indoor and outdoor units, including cabinet, coils, and fans.

Chapter 2: Mechanical Installation

2.1. Unpacking and Inspection

Guides on how to unpack and inspect the Liebert SRC-G unit components after delivery.

2.2. Installation Notes

Provides important considerations and recommendations for the installation of the Liebert SRC-G unit.

2.6. Indoor Unit Installation Procedure

Outlines the steps and requirements for installing the indoor unit, including room and space considerations.

2.8. Refrigeration Piping Connection General Principles

Explains the general principles and requirements for connecting the refrigeration piping for the unit.

Chapter 3: Electrical Installation

3.2. Installation Notes

Lists essential notes and regulations for power and control cabling, and ground connections.

3.3. Indoor Unit Connection

Details the procedure for connecting power supply and control cables to the indoor unit.

3.4. Outdoor Unit Connection

Explains how to connect the cables to the outdoor unit's terminal block.

Chapter 4: Start-up Commissioning

4.1. Start-up Inspection

Lists inspection requirements for unit components before commissioning to ensure proper operation.

4.2. Function Testing

Describes how to perform function testing for cooling and dehumidifying modes of the unit.

Chapter 5: Controller Operation Instructions

5.1. Feature

Highlights the features of the microprocessor controller, including display, password protection, and communication.

5.3. Control Interface

Explains the control interface, including function buttons and their operations.

5.4. Menu Structure

Details the menu structure, including alarm, setpoint, system status, and help menus.

5.7. System Menu

Covers system setup, outdoor unit options, and optional functions within the controller menu.

Chapter 6: System Operation and Maintenance

6.1. Electrical Inspection

Guides on inspecting electrical components like control boards, power boards, and connections.

6.2. Indoor Unit Maintenance

Covers maintenance procedures for the indoor unit, including filter, fan, and drain pipe.

6.4. Monthly Routine Maintenance

Lists monthly inspection items for system components to ensure normal function and check for wear.

Chapter 7: Troubleshooting

Troubleshooting Common Issues

Provides a guide for troubleshooting common issues like unit not starting, no cooling, and display anomalies.