How to fix a high pressure alarm on Vertiv Air Conditioner?
- DDarlene WardAug 26, 2025
To address a high pressure alarm on your Vertiv Air Conditioner, start by checking for sufficient airflow across the condenser. Remove any debris from the coil and airflow inlet, and check the fan speed function of the control board. Also, inspect the condenser fan to ensure it is operating; check that the connections of the control board to the outdoor unit terminals are firmly connected and that the condensate pressure sensor works normally. Lastly, examine the high-pressure switch and its connections, checking its on-off condition when the power is turned off; if necessary, replace it with a high-pressure switch of the same specification.