Chapter 5: Detailed description of parameters
175
Properties of PID integration
Stop the integration when the output
reaches the required limit
Separate Integration
If separate Integration is enabled, the PID stops the operation when to X is assigned 38
"PID integration paused". In this case, only linear and differential operations are effective.
If separate integration is disabled, it does not matter whether or not the 38 "PID
Integrated Suspended" function assigned to S is enabled.
Integration is a stop when the output reaches the required limit. If "stop integration" is
selected, the PID integration operation stops, which can help reduce the PID parameter
overrun.
Detection of PID controller feedback loss
0.0%: loss of feedback is not detected
0.1%: 100.0%
Detection time when PID controller feedback is
lost
These parameters are used to assess the loss of PID feedback.
If the PID feedback is less than PA.26 and the continuous time exceeds PA.27, the inverter
reports Err31 and operates according to the selected failure protection action.
Správanie sa PID pri strate spätnej väzby
These parameters are used to assess the loss of PID feedback.
If the PID feedback is less than PA.26 and the total time exceeds PA.27, the inverter
reports PIDE and continues according to the selected failure protection action.