8 TECHNICAL SPECIFICATIONS
8.1 POWER DATA
Power Supply:
Tolerance: -15 % to +10 %.
Frequency: 50/60 Hz (48 Hz to 62 Hz).
Phase imbalance: ≤ 3 % of the rated phase-to-phase input voltage.
Overvoltage according to Category III (EM 61010/UL 508C).
Transient voltages according to Category III.
Maximum of 10 connections per hour (1 every 6 minutes).
Typical efficiency: ≥ 97 %.
Classification of chemically active substances: level 3C2.
Mechanical condition rating (vibration): level 3M4.
Audible noise level: < 60dB.
For further information about the technical specifications, refer to APPENDIX B - TECHNICAL
SPECIFICATIONS on page 113.