59305, Issue 5 – March 2005 Glossary Page 123
Retransmit Output 1 Scale Maximum Type: General Parameter
Scales a linear output module in slot 1 that has been set up to retransmit PV or SP.
Retransmit Scale Maximum defines the value of the process variable, or setpoint, at which
the output will be at its maximum value. E.g. for a 0 to 5V output, the value corresponds to
5V. It may be adjusted within the range -1999 to 9999; the decimal position is always the
same as that for the process variable input. If this parameter is set to a value less than that
for Retransmit Output 1 Scale Minimum, the relationship between the process
variable/setpoint value and the retransmission output is reversed.
Display code = 9"2), default value = Scale Range Upper Limit.
Also refer to Process Variable, Retransmit Output, Retransmit Output 1 Scale Minimum,
Scale Range Upper Limit and Setpoint.
Retransmit Output 1 Scale Minimum Type: General Parameter
Scales a linear output module in slot 1 that has been set up to retransmit PV or SP.
Retransmit Scale Minimum defines the value of the process variable, or setpoint, at which
the output will be at its minimum value. E.g. for a 0 to 5V output, the value corresponds to
0V. It may be adjusted within the range -1999 to 9999; the decimal position is always the
same as that for the process variable input. If this parameter is set to a value greater than
that for Retransmit Output Scale Maximum, the relationship between the process
variable/setpoint value and the retransmission output is reversed.
Display code = 9"2+, default value = Scale Range Lower Limit.
Also refer to Process Variable, Retransmit Output, Retransmit Output 1 Scale Maximum,
Scale Range Lower Limit and Setpoint.
Retransmit Output 2 Scale Maximum Type: General Parameter
Defines the value of the process variable, or setpoint, at which Retransmit Output 2 will be at
its maximum value. It is similar to Retransmit Output 1 Scale Maximum.
Display code = 9"3), default value = Scale Range Upper Limit.
Also refer to Process Variable, Retransmit Output, Retransmit Output 2 Scale Minimum,
Scale Range Upper Limit and Setpoint.
Retransmit Output 2 Scale Minimum Type: General Parameter
Defines the value of the process variable, or setpoint, at which Retransmit Output 2 will be at
its minimum value. It is similar to Retransmit Output 1 Scale Minimum.
Display code = 9"3+, default value = Scale Range Lower Limit.
Also refer to Process Variable, Retransmit Output, Retransmit Output 2 Scale Maximum,
Scale Range Lower Limit and Setpoint.
Retransmit Output 3 Scale Maximum Type: General Parameter
Defines the value of the process variable, or setpoint, at which Retransmit Output 3 will be at
its maximum value. It is similar to Retransmit Output 1 Scale Maximum.
Display code = 9"4), default value = Scale Range Upper Limit.
Also refer to Process Variable, Retransmit Output, Retransmit Output 3 Scale Minimum,
Scale Range Upper Limit and Setpoint.