- DIN Controllers & Indicators - Product Manual
59305, Issue 5 – March 2005 P6100, P8100 & P4100 Model Group Page 45
Table 12. P6100, P8100 & P4100 Set Up Mode Parameters
Parameter Lower
Display
Upper Display
Adjustment Range
Default
Value
When
Visible
Input Filter Time
constant
&<+#'
OFF, 0.5 to 100.0 secs in
0.5 sec increments
3. @'
Always
Process Variable Offset
,&&:'
±Span of controller
@'
Always
Primary Power
--Ww
The current Primary
Output Power. Read Only.
N/A
Always
Secondary Power
:-Ww
The current Secondary
Output power. Read Only.
N/A
$#C1 = D=5+'
Primary Output
Proportional Band
-6B-'
0.0% (ON/OFF control)
and 0.5% to 999.9% of
input span.
2@. @'
Always
Secondary Output
Proportional Band
-6B:'
0.0% (ON/OFF control)
and 0.5% to 999.9% of
input span.
2@. @'
$#C1 = D=5+'
Automatic Reset
(Integral Time
Constant)
59J#'
1 sec to 99 mins 59 secs
and OFF
G. @@'
-6B-
'
is not
@. @'
Rate (Derivative Time
Constant)
95K.'
00 secs to 99 mins 59
secs
2. 2G'
-6B-
'
is not
@. @'
Overlap/Deadband
,+'
-20% to +20% of the sum
of the Primary and
Secondary Proportional
Bands
@'
-6B-
'
is not
@.@'
Manual Reset (Bias)
6<5:'
0% to 100% (-100% to
100% if
$#C1 = D=5+)
3G'
-6B-
'
is not
@. @'
Primary Output
ON/OFF Differential
D<&-'
0.1% to 10.0% of input
span (enter in % span)
@. G'
-6B-
= @. @'
Secondary Output
ON/OFF Differential
D<&:'
0.1% to 10.0% of input
span (enter in % span)
@. G'
-6B:
= @. @'
Primary and Secondary
Output ON/OFF
Differential
D<&&'
0.1% to 10.0% of input
span (enter in % span)
@. G'
-6B-
and -6B:
=
@. @'
Setpoint Upper Limit
:-=+'
Current Setpoint value to
Scale Range Maximum
Range
Max.
Always
Setpoint Lower limit
:-++'
Scale Range Minimum to
current Setpoint value
Range Min Always
Primary (Heat) Output
Upper Power Limit
,-=+'
0% to 100% of full power
2@@'
-6B-
'
is not
@. @'
Output 1
Cycle Time
$K2'
0.5, 1, 2, 4, 8, 16, 32, 64,
128, 256 or 512 secs.
Not applicable to linear
outputs
43'
>:.2
= -9<'
or :;?''
or
6=J