EasyManua.ls Logo

Xtreme TX90 6kVA - Calibration from the Front Panel

Xtreme TX90 6kVA
101 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Xtreme Power Conversion Corporaon
TX90 6kVA & 10kVA Service Manual
Page 29
Uninterrupble Power Supply
Calibraon from the Front Panel
Noce: For No load Inverter calibraon, you are required to use the seng soware to do it. The Calibraon from
the front panel is just only for the calibraon with load connected.
Connect the UPS as gure.
Connect a AC 1φ220Vac/50(60)Hz / 3φ380Vac/50(60)Hz source to the UPS input and adjust the charging
voltage to 273.7Vdc. (Make sure the baeries are disconnected.)
Turn on CB1 & CB2, Press key & key on the front panel simultaneously to make the UPS into the cali-
braon mode (The “N+1”LED lit means the UPS is working under Calibraon Step 1 now).
Use key key key & key on the front panel to proceed calibraon and seng.
Enter correct voltage & load%, then press key to go into self-calibraon.
The funcons of those key pads are:
key: +/- adjustment
key: next item
key: Your adjustments are done completely, new data is wrien into EEPROM, then Escape from the Cali-
braon mode. If the UPS beeps twice, it means your Seng is successful; on the contrary, if the UPS beeps
connuously, it means your seng is in failure.
key: Give up this calibraon and turn o the UPS.
Adjustable Parameters
Adjustable Items Specicaons Remarks
AC Input Voltage 1φ220Vac(3φ380Vac) Including Reced & Bypass input
Inverter Voltage 220Vac
Load % >30%
Baery Voltage 273.0Vdc
The UPS will escape from the calibraon mode if the calibraon is not nished in 10 minutes and go to
shutdown automacally and show “Line OFF” on LCD panel.
Tuning the values shown on the LCD display are the same as that on the meter, then you may go to next
Calibraon item.
The load% on LCD panel means the higher value of VA or W; therefore, you are recommended to use Re-
sistance Load to go for calibraon. To make sure the calibraon is precisely, you are also recommended to
use full load to calibraon the UPS
The sequence of the LCD display is shown as Output Volt ← → LOAD%.
Aer all the items desired are calibrated, press key and write them into EEPROM.
When the UPS beeps twice, the UPS will go to shutdown and show “Line OFF”on the LCD panel.
And then re-start the UPS to check if all values which have been calibrated on the LCD panel is the same
as those on the Power Meter.
If the buzzer beeps intermiently and connuously, it means your calibraon is in failure.
Cauon:
You are suggested to connect with 80% to 100% load in order to make sure the tolerance of the calibrated
values will be smaller and the values will be more accurate. All values can be calibrated except the value
of load% if the output load of UPS are less than 30% when you proceed calibrated acon.
Make sure the tolerance of the adjustable range will be less than 8% for Voltage and 15% for Load; other-
wise, the seng will be in failure and the error code will be shown on the LCD panel.
The values of both “load%” and “output voltage” must be round to Integer.

Related product manuals