3.2 Operating Procedures for Utility Functions
3.2.24 Reset Motor Type Change Detected Status (Fn021)
3-60
3.2.24
Reset Motor Type Change Detected Sta-
tus (Fn021)
After an A.070 (Motor Type Change Detected) alarm occurs, you must
reset the Motor Type Change Detected status.
Preparations
Always check the following before you reset the Motor Type Change
Detected.
The parameters must not be write-prohibited (Fn010 must be set to
0000).
An A.070 (Motor Type Change Detected) alarm must have occurred.
Operating Procedure
Step Operation Result
1
Press the Key to display the
Utility Mode Main Menu, and then
use the Key or Key to
select Fn021.
2
Press the Key.
The Motor Type Change Detected
status will be reset.
When processing has been com-
pleted, the status display will flash
DONE for approximately one sec-
ond and then return to 1:A.070.
3
Press the Key.
The display will return to the Utility
Mode Main Menu.
4
Turn the SERVOPACK power sup-
ply OFF and ON again.
The parameter setting is now
enabled and the alarm will have
been cleared.
1:A.070 FUNCTION
Fn020 : S -Orig S et
F n 0 2 1 : Motor
lnit
Fn03 0 : S oft Res et
F n 0 8 0 : Pole Detect
1:A.070
Motor Connect
His try lnit
S tart : [DATA]
Return: [S ET]
1:A.070 FUNCTION
Fn020 : S -Orig S et
F n 0 2 1 : Motor
lnit
Fn03 0 : S oft Res et
F n 0 8 0 : Pole Detect

Table of Contents

Other manuals for YASKAWA E-7 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA E-7 Series and is the answer not in the manual?

YASKAWA E-7 Series Specifications

General IconGeneral
BrandYASKAWA
ModelE-7 Series
CategoryServo Drives
LanguageEnglish

Related product manuals