3.2 Operating Procedures for Utility Functions
3.2.43 INDEXER Alarm Reset (FnB0C)
3-134
3.2.43
INDEXER Alarm Reset (FnB0C)
This function resets alarms at both the SERVOPACK and INDEXER
Module, and clears the alarm history at the INDEXER Module.
Preparation
When Resetting Alarms
None
When Clearing the Alarm History
Always check the following before you clear the alarm history.
• The parameters must not be write-prohibited (Fn010 must be set to
0000).
• The ALMTRCCLR command must not being executed.
• The RES command must not being executed.
Operating Procedure
• INDEXER Module alarms are not reset by the “ALARM RESET”
button of the digital operator. To reset INDEXER Module alarms,
execute alarm resetting with FnB0C.
• Eliminate the causes of alarms before resetting them.
• When you execute Fn006, only the SERVOPACK alarm history is
cleared. The INDEXER Module alarm history is not cleared. To
clear the INDEXER Module alarm history, execute alarm history
clearance with FnB0C.
Step Operation Result
1
Press the key to open the Util-
ity Function Mode main menu, and
move the cursor with the
keys to select FnB0C.
2
Press the key to view the
FnB0C operation screen.
Continued on next page.