3.2 Operating Procedures for Utility Functions
3.2.32 Vibration Suppression (Fn205)
3-100
3.2.32
Vibration Suppression (Fn205)
You can use this utility function to suppress transitional vibration at a low
frequency from 1 to 100 Hz, which is generated mainly when the
machine vibrates during positioning.
Vibration suppression is set automatically when advanced autotuning or
advanced autotuning with a reference input is executed. In most cases,
this utility function is not necessary. Use this utility function only if fine-
tuning is required or readjustment is required as a result of a failure to
detect vibration.
Perform one-parameter tuning (Fn203) if required to improve the
response after performing this utility function.
Preparations
Always check the following before you execute vibration suppression.
The parameters must not be write-prohibited (Fn010 must be set to
0000).
The servo must be in ready status.
There must be no overtravel.
Position control must be used.
Tuning-less function must be disabled (Pn170 = n.
0).
The test without a motor function must be disabled (Pn00C =
n.
0).

Table of Contents

Other manuals for YASKAWA E-7 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA E-7 Series and is the answer not in the manual?

YASKAWA E-7 Series Specifications

General IconGeneral
BrandYASKAWA
ModelE-7 Series
CategoryServo Drives
LanguageEnglish

Related product manuals