B.1 European Standards
YASKAWA ELECTRIC TOEP C710687 02B FSDrive-MV1000 Instructions 221
n Grounding
Grounding terminals that are indicated as EA and ED in this manual are equivalent to those indicated as PE and PE (ED)
in European standards. When connecting the grounding terminals, observe the precautions and follow the procedures
outlined in this manual to ensure safety.
To comply with EMC guidelines, be sure that the PE and PE (ED) grounding terminals are separately connected.
n
Connection of the Limit Switch
To ensure safety, door limit switches are provided in the panel. Door limit switches that detect opening of the panel door
are provided in the drive as a measure to ensure safety. Be sure to correctly connect cables for this circuit. After
connecting the cables, confirm that primary switch gear will be tripped when the doors are open.
n
Dimensions
Dimensions and approximate masses of CE-marking-conforming products are shown below.
Table B.1 Drive Dimensions and Approximate Masses
Figure B.2
Figure B.2 Dimension Drawing (Class: 6 kV)
Voltage
Class
(kV)
Model
CIMR-MV2C
Dimensions (mm)
Approx.
Mass
(kg) <3>
Dimension
Drawing
No.
Width Depth Height Height Height
W D H H1 H2
6
F5FA035 <1> <2>
<1> Side-by-side configurations comprising two or more drive panels
<2> Under development
<3> The dimensions and masses are subject to change.
Figure B.2
3100 1100 2550 2150 400 3600
F5FA050 <1> <2>
3100 1100 2550 2150 400 4000
F5FA070 <1> <2>
3100 1100 2550 2150 400 4300
F5FA100 <1> <2>
3100 1100 2550 2150 400 4700
F5FA140 <1> <2>
3100 1100 2550 2150 400 5000
F5FA200 <1> <2>
4500 1300 2550 2150 400 7400
F5FA260 <1> <2>
5500 1300 2550 2150 400 8800
F5FA330 <1> <2>
6300 1600 2800 2400 400 10500
F5FA400 <1> <2>
6300 1600 2800 2400 400 11300
F5FA520 <1> <2>
7100 1600 2800 2400 400 13500
F5FA650 <1> <2>
7300 1600 2800 2400 400 15200
Max.
800 mm
D
Door opening
dimension
H2H1
H