2.1 A: Initialization
100 YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
u A3: Trace Data
A3 parameters are used for the Trace function of the Drive Wizard Plus MV.
n
A3-01 to A3-32: Trace Data 01 to 32
Sets up to 32 numbers of monitor items to be registered as the trace data.
Note: 1. Set this parameter to the last three digits - of the desired U- parameter. For example, enter “103” for U1-03 (output
current).
2. Set “000” if the parameter is not used.
3. When a CPF00, CPF01, CPF06, Uv1, oFA00, oFb00, or oFC00 fault occurs, no fault trace is performed.
n A3-33: High-Speed Trace Sampling Time
Sets the sampling time for high-speed tracing in 0.001 s units. A setting of 0.000 s is equal to 0.00025 s (250 μs).
Note: 1. The maximum number of sampling points for high-speed tracing is 4000 per item.
2. When a CPF00, CPF01, CPF06, Uv1, oFA00, oFb00, or oFC00 fault occurs, no fault trace is performed.
n A3-34: Low-Speed Trace Sampling Time
Sets the sampling time for low-speed tracing in 0.01s units.
Note: 1. The maximum number of sampling points for low-speed tracing is 500 per item.
2. When a CPF00, CPF01, CPF06, Uv1, oFA00, oFb00, or oFC00 fault occurs, no fault trace is performed.
n A3-35: Number of Data after High-Speed-Trace Fault Detection
Sets the number of samplings of the data to be registered after a fault is detected in high-speed tracing.
Note: 1. Only effective when a fault has been detected and operation automatically stopped.
2. When a CPF00, CPF01, CPF06, Uv1, oFA00, oFb00, or oFC00 fault occurs, no fault trace is performed.
n A3-36: Number of Data after Low-Speed-Trace Fault Detection
Sets the number of samplings of the data to be registered after a fault is detected in low-speed tracing.
Note: 1. Only effective when a fault has been detected and operation automatically stopped.
2. When a CPF00, CPF01, CPF06, Uv1, oFA00, oFb00, or oFC00 fault occurs, no fault trace is performed.
n A3-37: Trace Stop Selection
Sets the condition to stop tracing.
Note: When a CPF00, CPF01, CPF06, Uv1, oFA00, oFb00, or oFC00 fault occurs, no fault trace is performed.
Setting 0: Error always detected and drive stopped
Setting 1: Error detected and drive stopped during Run only
No.
<1> Refer to Control Mode Dependent Parameter Default Values on page 84 for details on the default settings.
Name Setting Range Default
A3-01 to A3-32 Trace Data 01 to 32 0 to 899 Determined by A1-02 <1>
No. Name Setting Range Default
A3-33 High-Speed Trace Sampling Time 0.000 to 10.000 s 0.000 s
No. Name Setting Range Default
A3-34 Low-Speed Trace Sampling Time 0.01 to 60.00 s 0.05 s
No. Name Setting Range Default
A3-35
Number of Data after High-Speed-Trace Fault
Detection
0 to 250 200
No. Name Setting Range Default
A3-36
Number of Data after Low-Speed-Trace
Fault Detection
0 to 250 50
No. Name Setting Range Default
A3-37 Trace Stop Selection 0 or 1 0
MV1000ParameterGuide_E_conditional.book 100 ペー 01年1月1日 日 午後8時18分