2.7 H: Terminal Functions
200 YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
Using Gain and Bias to Adjust Output Signal Level
The meter can be calibrated while the drive is stopped.
The procedure for calibration is as follows.
Analog Output 1
1. View the value set to H4-02 (Analog Output 1 Gain) on the digital operator. A voltage equal to 100% of the
parameter being set in H4-01 will be output from analog output 1.
2. Adjust H4-02 viewing the monitor connected to the analog output 1.
3. View the value set to H4-03 on the digital operator, analog output 1 will output a voltage equal to 0% of the
parameter being set in H4-01.
4. Adjust H4-03 viewing the output signal on the analog output 1.
Analog Output 2
1. View the value set to H4-12 (Analog Output 2 Gain) on the digital operator. A voltage equal to 100% of the
parameter being set in H4-11 will be output from analog output 2.
2. Adjust H4-12 viewing the monitor connected to the analog output 2.
3. View the value set to H4-13 on the digital operator, analog output 2 will output a voltage equal to 0% of the
parameter being set in H4-11.
4. Adjust H4-13 viewing the output signal on the analog output 2.
Analog Output 3
1. View the value set to H4-22 (Analog Output 3 Gain) on the digital operator. A voltage equal to 100% of the
parameter being set in H4-21 will be output from analog output 3.
2. Adjust H4-22 viewing the monitor connected to the analog output 3.
3. View the value set to H4-23 on the digital operator, analog output 3 will output a voltage equal to 0% of the
parameter being set in H4-21.
4. Adjust H4-23 viewing the output signal on the analog output 3.
Analog Output 4
1. View the value set to H4-32 (Analog Output 4 Gain) on the digital operator. A voltage equal to 100% of the
parameter being set in H4-31 will be output from analog output 4.
2. Adjust H4-32 viewing the monitor connected to the analog output 4.
3. View the value set to H4-33 on the digital operator, analog output 4 will output a voltage equal to 0% of the
parameter being set in H4-31.
4. Adjust H4-33 viewing the output signal on the analog output 4.
n
H4-05, H4-15, H4-25, H4-35: Analog Output 1, 2, 3, 4 Signal Level Selection
Parameters H4-05, H4-15, H4-25, and H4-35 set the voltage output level of U monitor parameter data to analog output
terminals 1 to 4.
u H5: MEMOBUS/Modbus Serial Communication
Through the built-in RS-485 port of the drive (terminals R+, R-, S+, S-), serial communication is possible using
programmable logic controllers (PLCs) or similar devices running the MEMOBUS/Modbus protocol.
The H5- parameters are used for the drive settings when using MEMOBUS/Modbus communications. For details,
refer to the FSDrive-MV1000 Instructions (Manual No. TOEP C710687 02).
No. Name Setting Range Default
H4-05 Analog Output 1 Signal Level Selection 0 or 1 1
H4-15 Analog Output 2 Signal Level Selection 0 or 1 1
H4-25 Analog Output 3 Signal Level Selection 0 or 1 1
H4-35 Analog Output 4 Signal Level Selection 0 or 1 1