1.3 Parameter Table
YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide 63
Note: The settings for MEMOBUS/Modbus communications take effect after cycling power.
u L: Protection Function
L parameters provide protection to the drive and motor, such as: control during momentary power loss, main power
supply, Stall Prevention, frequency detection, fault restarts, overtorque detection, torque limits, and other types of
hardware protection.
H5-05
(429H)
Communication
Fault Detection
Selection
0: Disabled
1: Enabled. If communication is lost for more than the time set in H5-09, a
CE fault will occur.
Default: 1
Min: 0
Max: 1
<38>
H5-06
(42AH)
Drive Transmit Wait
Time
Set the wait time between receiving and sending data.
Default: 5 ms
Min: 5 ms
Max: 65 ms
<38>
H5-07
(42BH)
RTS Control
Selection
0: Disabled. RTS is always on.
1: Enabled. RTS turns on only when sending.
Default: 1
Min: 0
Max: 1
<38>
H5-09
(435H)
CE Detection Time
Sets the time required to detect a communications error.
Adjustment may be needed when networking several drives.
Default: 2.0 s
Min: 0.0 s
Max: 10.0 s
<38>
H5-11
(43CH)
Communications
ENTER Function
Selection
0: Drive requires an Enter command before accepting any changes to
parameter settings.
1: Parameter changes are activated immediately without the Enter command.
Default: 0
Min: 0
Max: 1
<38>
H5-12
(43DH)
Run Command
Method Selection
0: FWD/Stop, REV/Stop
1: Run/Stop, FWD/REV
Default: 0
Min: 0
Max: 1
<38>
<32> If this parameter is set to 0, the drive will be unable to respond to MEMOBUS/Modbus commands.
<38> For details, refer to the FSDrive-MV1000 Instructions (Manual No. TOEP C710687 02).
No.
(Addr.)
Name Description Setting Page
L1: Motor Protection
L1-01
(480H)
Motor Overload
Protection Selection
0: Disabled
1: Enabled
The drive may not be able to provide protection when using multiple motors,
even if overload protection is enabled in L1-01. Set L1-01 to 0 and install
separate thermal relays to each motor.
Default:
<10>
Min: 0
Max: 1
201
L1-02
(481H)
Motor Overload
Protection Time
Sets the motor thermal overload protection (oL1) time.
Default: 60.0 s
Min: 1.0 s
Max: 300.0 s
202
L1-06
(3120H)
Motor Overload
Detection Start
Level
Sets the start level for motor overload detection as a percentage of the motor
rated current. Set a value lower than the value for L1-07.
Default: 110%
Min: 20%
Max: 300%
202
L1-07
(3121H)
Motor Overload
Detection Level
Sets the level at which motor overload is detected as a percentage of the
motor rated current. Set a value higher than the value for L1-06.
Default: 150%
Min: 30%
Max: 300%
202
L1-13
(46DH)
Continuous
Electrothermal
Operation Selection
0: Disabled
1: Enabled
Default: 1
Min: 0
Max: 1
202
No.
(Addr.)
Name Description Setting Page
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
MV1000ParameterGuide_E_conditional.book 63 ページ 013年10月11日 金曜日 午後8時18分