1.5 Defaults by Drive Model Selection (o2-04)
YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide 87
1.5 Defaults by Drive Model Selection (o2-04)
The following tables show parameters and default settings that change with the drive model selection (o2-04). Parameter
numbers shown in parenthesis are valid for motor 2.
Table 1.4 2.4 kV Class Drives Default Settings by Drive Model Selection
No. <61> Name Unit Default Settings
–
Model
CIMR-
MV2
–
052 068 080 093 102 115 135 160 180 205 220 280 330 390 440 505 550 600
o2-04
Drive Model
Selection
–
00 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0F 10 11
E2-11
(E4-11)
Motor Rated
Power
kW
(HP)
170
(228)
190
(255)
260
(349)
310
(416)
340
(456)
380
(509)
450
(603)
530
(710)
600
(804)
680
(912)
730
(979)
930
(1247)
1100
(1475)
1300
(1743)
1460
(1957)
1680
(2252)
1830
(2453)
2000
(2681)
b3-04
V/f Gain during
Speed Search
%
80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80
b3-06
Output Current 1
during Speed
Search
–
0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
b3-11
Speed Search
Method
Switching Level
(Speed Estimate
Type Speed
Search)
%
5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0
E2-01
(E4-01)
Motor Rated
Current
A
40.0 50.0 70.0 80.0 90.0 100.0 110.0 140.0 150.0 170.0 190.0 240.0 280.0 330.0 370.0 430.0 470.0 510.0
E2-02
(E4-02)
Motor Rated Slip Hz
0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25
E2-03
(E4-03)
Motor No-Load
Current
A
10.0 13.0 18.0 20.0 23.0 25.0 28.0 35.0 38.0 43.0 48.0 60.0 70.0 83.0 93.0 108.0 118.0 128.0
E2-05
(E4-05)
Motor
Line-to-Line
Resistance
W
0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300
E2-06
(E4-06)
Motor Leakage
Inductance
%
20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0
E2-10
(E4-10)
Motor Iron Loss
for Torque
Compensation
W
00000000000 0 0 0 0 0 0 0
L2-02
Momentary
Power Loss
Ride-Thru Time
s
2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
L2-03
Momentary
Power Loss
Ride-Thru
Minimum
Baseblock Time
s
2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
L2-04
Momentary
Power Loss
Ride-Thru
Voltage Recovery
Time
s
5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0
L2-05
Undervoltage
Detection Level
(Uv)
V
693 693 693 693 693 693 693 693 693 693 693 693 693 693 693 693 693 693
L8-02
<62>
Overheat Alarm
Level
–
105 105 105 105 105 105 105 105 105 105 95 105 105 105 100 100 105 105
L8-09
Output Ground
Fault Detection
Selection
–
11111111111 1 1 1 1 1 1 1
L8-33
FAN Board Use
Selection
–
11111112222 2 2 2 2 2 2 2