2.6 F: Option Settings
166 YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
u F3: Contact Input Card Settings
These parameters set the drive for operation with the option card DI-A3. This section describes parameters that govern
operation with a contact input option card. Refer to the instruction manual packaged with the option card for specific
details on installation, wiring, input signal level selection, and parameter setup.
n
F3-01: Contact Input Option Card Input Selection
Determines the type of input for contact input option card DI-A3 when o1-03 is set to 0 or 1.
Setting 0: BCD, 1% units
Setting 1: BCD, 0.1% units
Setting 2: BCD, 0.01% units
Setting 3: BCD, 1 Hz units
Setting 4: BCD, 0.1 Hz units
Setting 5: BCD, 0.01 Hz units
Setting 6: BCD, special setting (5-digit input), 0.02 Hz units
Setting 7: Binary
The units and setting range are determined by the setting for F3-03 as shown below.
F3-03 = 0: 100%/255 (-255 to +255)
F3-03 = 1: 100%/4095 (-4095 to +4095)
F3-03 = 2: 100%/30000 (-33000 to +33000)
Note: When o1-03 = 2 or 3, the input is BCD regardless of the setting for F3-01, and the units are determined by parameter o1-03.
n F3-03: Contact Input Option DI-A3 Data Length Selection
Determines the number of bits for the option card input that sets the frequency reference.
Setting 0: 8 bit
Setting 1: 12 bit
Setting 2: 16 bit
u F4: Analog Monitor Card Settings
These parameters set the drive for operation with the analog output option card AO-A3. This section describes
parameters that govern operation with an analog output option card. Refer to the instruction manual packaged with the
option card for specific details on installation, wiring, input signal level selection, and parameter setup.
n
F4-01: Analog Output 5 (Terminal V1) Monitor Selection
Selects the data to output from analog output 5 (terminal V1). Enter the final three digits of U- to determine which
monitor data is output from the option card. Some monitors are only available in certain control modes.
n
F4-02: Analog Output 5 (Terminal V1) Gain
Parameter F4-02 determines the gain. This parameter is set as a percentage of the output signal from analog output 5
(terminal V1) where 100% equals 10 V output. The terminal output voltage is limited to 10 V.
No. Name Setting Range Default
F3-01 Contact Input Option Card Input Selection 0 to 7 0
No. Parameter Name Setting Range Default
F3-03 Contact Input Option DI-A3 Data Length Selection 0 to 2 2
No. Name Setting Range Default
F4-01 Analog Output 5 (Terminal V1) Monitor Selection 000 to 999 102
No. Name Setting Range Default
F4-02 Analog Output 5 (Terminal V1) Gain -999.9 to 999.9% 100.0%