1.4 Control Mode Dependent Parameter Default Values
86 YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
u E3-01 (Motor 2 Control Mode) Dependent Parameters
Table 1.3 E3-01 (Motor 2 Control Mode) Dependent Parameters and Default Values
No. Name Setting Range Resolution
Control Modes (E3-01)
V/f (0) OLV (2) CLV (3)
C3-21 Motor 2 Slip Compensation Gain 0.0 to 2.5 0.1 0.0 1.0 1.0
C3-22 Motor 2 Slip Compensation Primary Delay Time 0 to 10000 1 ms 3000 3000 –
C4-07 Motor 2 Torque Compensation Gain 0.00 to 2.50 0.01 1.00 1.00 –
C4-08
Motor 2 Torque Compensation Primary Delay
Time
0 to 10000 1 ms 200 50 –
C5-21 Motor 2 ASR Proportional Gain 1 0.00 to 300.00 0.01 – – 5.00
C5-22 Motor 2 ASR Integral Time 1 0.000 to 10.000 0.001 s – – 5.000
C5-23 Motor 2 ASR Proportional Gain 2 0.00 to 300.00 0.01 – – 5.00
C5-24 Motor 2 ASR Integral Time 2 0.000 to 10.000 0.001 s – – 5.000
C5-26 Motor 2 ASR Primary Delay Time Constant 0.0 to 0.500 0.001 s – – 0.004
E3-04 Motor 2 Maximum Output Frequency 40.0 to 120.0 0.1 Hz 60.0 60.0 60.0
E3-05 Motor 2 Maximum Voltage 0 to 13000 1 V 2000 2000 2000
E3-06 Motor 2 Base Frequency 0.0 to 120.0 0.1 Hz 60.0 60.0 60.0
E3-07 Motor 2 Mid Output Frequency 0.0 to 120.0 0.1 Hz 3.0 3.0 0.0
E3-08 Motor 2 Mid Output Frequency Voltage 0 to 13000 1 V 150 110 0
E3-09 Motor 2 Minimum Output Frequency 0.0 to 120.0 0.1 Hz 1.5 0.5 0.0
E3-10 Motor 2 Minimum Output Frequency Voltage 0 to 13000 1 V 90 20 0
MV1000ParameterGuide_E_conditional.book 86 ページ 2013年10月11日 金曜日 午後8時18分