2.10 o: Operator Related Settings
236 YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
Setting 0: Copy Select (no function)
Setting 1: INV --> OP READ
All parameters are copied from the drive to the digital operator.
Setting 2: OP --> INV WRITE
All parameters are copied from the digital operator to the drive.
Setting 3: OP<-->INV VERIFY
Parameters in the drive are compared with the parameter settings saved on the digital operator to see if they match.
n
o3-02: Copy Allowed Selection
Restricts or allows the use of the Copy function.
Setting 0: Disabled
Setting 1: Enabled
u o4: Maintenance Monitor Settings
n o4-01: Cumulative Operation Time Setting
Sets the cumulative operation time of the drive. The user can also manually set this parameter to begin keeping track of
operation time from some desired value. Total operation time can be viewed in monitor U4-01.
Note: The value in o4-01 is set in 10 h units. For example, a setting of 30 will set the cumulative operation time counter to 300 h. 300 h
will also be displayed in monitor U4-01.
n o4-02: Cumulative Operation Time Selection
Selects the conditions for how the drive keeps track of its total operation time. This time log can be viewed in U4-01.
Setting 0: Power on time
The drive logs the time it is connected to a power supply, regardless of whether the motor is running.
Setting 1: Run time
The drive logs the time that the output is active. This includes whenever the Run command is active (even if the motor is
not rotating) and when there is voltage output.
n
o4-11: U2, U3 Initialization
Resets the fault trace and fault history monitors (U2- and U3-). Initializing the drive using A1-03 does not reset
these monitors.
Setting 0: No action
The drive keeps the record already saved concerning fault trace and fault history.
Setting 1: Reset fault data
Resets the data for the U2- (Fault Trace) and U3- (Fault History) monitors. When o4-11 is set to 1 and the
ENTER key is pressed, fault data is erased and the setting of the parameter returns to 0.
No. Name Setting Range Default
o3-02 Copy Allowed Selection 0, 1 0
No. Name Setting Range Default
o4-01 Cumulative Operation Time Setting 0 to 9999 0
No. Name Setting Range Default
o4-02 Cumulative Operation Time Selection 0, 1 0
No. Name Setting Range Default
o4-11 U2, U3 Initialization 0, 1 0
MV1000ParameterGuide_E_conditional.book 236 ペー 01年1月1日 日 午後8時18分