26 YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
u b: Application
Application parameters configure the source of the Run command, DC Injection Braking, Speed Search, timer functions,
PID control, the Dwell function, and a variety of other application-related settings.
<3> Parameter setting value is not reset to the default value when the drive is initialized (A1-03 = 1110/2220).
<10> Default setting is determined by A1-02, Control Method Selection.
<68> This setting is available for digital operator JVOP-180 versions REV: F and later.
No.
(Addr.)
Name Description Setting Page
b1: Operation Mode Selection
b1-01
(180H)
Frequency
Reference Selection
1
0: Digital operator
1: Analog input terminals
2: MEMOBUS/Modbus communications
3: Option board
Default: 1
Min: 0
Max: 3
101
b1-02
(181H)
Run Command
Selection 1
0: Digital operator
1: Control circuit terminal (contact input)
2: MEMOBUS/Modbus communications
3: Option PCB
Default: 1
Min: 0
Max: 3
102
b1-03
(182H)
Stopping Method
Selection
0: Ramp to stop
1: Coast to stop
2: DC Injection Braking to stop
3: Coast with timer
Default: 1
Min: 0
Max: 3
<11>
103
b1-04
(183H)
Reverse Operation
Selection
0: Reverse enabled.
1: Reverse disabled.
Default: 1
Min: 0
Max: 1
105
b1-05
(184H)
Action Selection
below Minimum
Output Frequency
(E-09)
0: Operates according to frequency reference (E1-09 is disabled).
1: Ramp to Stop
2: Operates according to E1-09 (frequency reference set to E1-09).
3: Zero speed (frequency reference becomes zero when less than E1-09).
Default: 0
Min: 0
Max: 3
105
b1-06
(185H)
Contact Input
Reading
0: Input status is read once every ms and processed immediately (for quick
response)
1: Input status is read twice every ms and processed only if the status is the
same in both readings (robust against signals with electrical interference)
Default: 1
Min: 0
Max: 1
106
b1-07
(186H)
LOCAL/REMOTE
Run Selection
0: An external Run command must be cycled at the new source to be
activated.
1: An external Run command at new source is accepted immediately.
Default: 0
Min: 0
Max: 1
107
b1-08
(187H)
Run Command
Selection while in
Programming Mode
0: Run command not accepted while in Programming Mode.
1: Run command accepted while in Programming Mode.
2: Prohibit entering Programming Mode during run.
Default: 0
Min: 0
Max: 2
107
b1-15
(1C4H)
Frequency
Reference Selection
2
Enabled when an input terminal set for “External reference” (H1- = 2)
closes.
0: Digital Operator
1: Analog input terminals
2: MEMOBUS/Modbus communications
3: Option board
Default: 0
Min: 0
Max: 3
107
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
CLV
V/f
OLV
common
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_