2.2 b: Application
YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide 105
n b1-04: Reverse Operation Selection
Enables and disables Reverse operation. For some applications, reverse motor rotation is not appropriate and may cause
problems (e.g., air handling units, pumps, etc.).
Setting 0: Reverse operation enabled
Possible to operate the motor in both forward and reverse directions.
Setting 1: Reverse operation disabled
The drive disregards a Reverse Run command or a negative frequency reference.
n
b1-05: Action Selection below Minimum Output Frequency (CLV)
Sets the operation when the frequency reference is lower than the minimum output frequency set in parameter E1-09.
Setting 0: Follow the Frequency Reference (E1-09 is disabled)
The drive adjusts the motor speed following the speed reference, even if the frequency reference is below the setting of
parameter E1-09. When a Stop command is input or the Run command is removed and the motor speed is smaller than
the setting of b2-01, Zero Speed Control (not position lock) is performed for the time set in parameter b2-04 before the
drive output shuts off.
Figure 2.6
Figure 2.6 Run at the Frequency Reference
Setting 1: Ramp to Stop
The motor is started first when the frequency reference exceeds the parameter E1-09 setting. When the motor is running
and the frequency reference falls below E1-09, the drive decelerates the motor to stop. When the motor speed falls below
the zero speed level set in b2-01, Zero Speed Control is activated for the time set in b2-04.
Figure 2.7
Figure 2.7 Ramp to Stop
No. Name Setting Range Default
b1-04 Reverse Operation Selection 0 or 1 1
No. Name Setting Range Default
b1-05 Action Selection below Minimum Output Frequency 0 to 3 0
Zero Speed
Control
b2-01 Zero
Speed Level
Run
Command
Frequency
reference
Motor
Speed
OFF ON
Zero Speed
Control
E1-09 Min.
Output Frequency
b2-04
DC Injection Braking (Zero
Speed Control) Time at Stop
E1-09
b2-03
DC Injection Braking (Zero
Speed Control)Time at Start
IM: Initial Excitation
common_TMonly
b2-03
DC Injection Braking (Zero
Speed Control) Time at Start
IM: Initial Excitation
b2-01 Zero
Speed Level
Run
Command
Frequency
reference
Motor
Speed
OFF ON
Zero Speed
Control
E1-09 Min.
Output Frequency
b2-04
DC Injection Braking (Zero
Speed Control) Time at Stop
common_TMonly
MV1000ParameterGuide_E_conditional.book 105 ペー 01年1月1日 日 午後8時18分