EasyManua.ls Logo

YASKAWA FSDrive-MV1000 - 2.2 b: Application; b1: Operation Mode Selection

YASKAWA FSDrive-MV1000
241 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2.2 b: Application
YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide 101
2.2 b: Application
u b1: Operation Mode Selection
n b1-01: Frequency Reference Selection 1
Selects the frequency reference source for the REMOTE mode.
Note: 1. If a Run command is input to the drive but the frequency reference entered is 0 or below the minimum frequency, the RUN indicator
LED on the digital operator will light.
2. Press the LO/RE key to set the drive to LOCAL and use the operator keypad to enter the frequency reference.
Setting 0: Operator keypad
Using this setting, the frequency reference can be input by:
switching between the multi-speed references in the d1- parameters.
entering the frequency reference on the operator keypad.
For details on how to change the setting value for the frequency reference, refer to the FSDrive-MV1000 Instructions
(Manual No. TOEP C710687 02).
Setting 1: Terminals (analog input terminals)
Using this setting, analog frequency references can be input as a voltage signal from analog input 1 or 2.
Make the settings as described in Tab le 2.6 for the input used.
Table 2.6 Analog Input Settings for Frequency Reference Using Voltage Signals
Switching between Main/Auxiliary Frequency References
The frequency reference input can be switched between analog input 1 and 2 using multi-speed inputs.
Refer to Multi-step Speed Reference and Contact Input Combinations on page 141 for details on using this function.
Setting 2: MEMOBUS/Modbus Communications
This setting requires entering the frequency reference via the RS-485 serial communications port (control terminals R+,
R-, S+, and S-). Refer to the FSDrive-MV1000 Instructions (Manual No. TOEP C710687 02) for details.
Setting 3: Option card
This setting requires entering the frequency reference via an option board plugged into connector CN5-A on the drive
control board. Consult the option board manual for instructions on integrating the drive with the communication system.
Note: If the frequency reference source is set for an option board (b1-01 = 3), but an option board is not installed, an oPE05 Operator
Programming Error will be displayed on the digital operator and the drive will not run.
No. Name Setting Range Default
b1-01 Frequency Reference Selection 1 0 to 3 1
Terminal Signal Level
Parameter Settings
Signal Level
Selection
Function Selection Gain Bias
Analog input 1
0 to 10 Vdc H3-01 = 0
H3-02 = 0
(Master Speed Frequency Reference)
H3-03 H3-04
-10 to +10 Vdc H3-01 = 1
Analog input 2
0 to 10 Vdc H3-09 = 0
H3-10 = 0
(Master Speed Frequency Reference)
H3-11 H3-12
-10 to +10 Vdc H3-09 = 1
MV1000ParameterGuide_E_conditional.book 101 ペー 01年1月1日 日 午後8時18分

Table of Contents

Other manuals for YASKAWA FSDrive-MV1000

Related product manuals