1.3 Parameter Table
YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide 75
u T: Motor Tuning
Enter data into the following parameters to tune the motor and drive for optimal performance
No.
(Addr.)
Name Description Setting Page
T1: Induction Motor Auto-Tuning
<6> Default setting is determined by o2-04, Drive Model Selection.
<10> Default setting is determined by A1-02, Control Method Selection.
<16> Default setting is determined by A1-02, Control Method Selection, and o2-04, Drive Model Selection.
<37> The availability of certain Auto-Tuning methods depends on the control mode selected for the drive.
<38> For details, refer to the FSDrive-MV1000 Instructions (Manual No. TOEP C710687 02).
T1-00
(700H)
Motor 1/Motor 2
Selection
1: Motor 1 (sets E1-, E2-)
2: Motor 2 (sets E3-, E4-)
Default: 1
Min: 1
Max: 2
<38>
T1-01
(701H)
<37>
Auto-Tuning Mode
Selection
0: Rotational Auto-Tuning
2: Stationary Auto-Tuning for Line-to-Line Resistance
Default:
<10>
Min: 0
Max: 2
<38>
T1-02
(702H)
Motor Rated Power
Sets the motor rated power as specified on the motor nameplate.
Note: Use the following formula to convert horsepower into
kilowatts: 1HP = 0.746 kW.
Default:
<6>
Min: 0 kW
Max: 65000 kW
<38>
T1-03
(703H)
Motor Rated Voltage
Sets the motor rated voltage as specified on the motor nameplate.
Default:
<16>
Min: 0 V
Max: 13000 V
<38>
T1-04
(704H)
Motor Rated Current
Sets the motor rated current as specified on the motor nameplate.
Default:
<6>
Min: 10% of drive
rated current
Max: 200% of
drive rated current
<38>
T1-05
(705H)
Motor Base
Frequency
Sets the rated frequency of the motor as specified on the motor nameplate.
Default: 60.0 Hz
Min: 0.0 Hz
Max: 120.0 Hz
<38>
T1-06
(706H)
Number of Motor
Poles
Sets the number of motor poles as specified on the motor nameplate.
Default: 4
Min: 2
Max: 48
<38>
T1-07
(707H)
Motor Base Speed
Sets the rated speed of the motor as specified on the motor nameplate.
Default: 1750 r/min
Min: 0 r/min
Max: 24000 r/min
<38>
T1-08
(708H)
PG Number of
Pulses Per
Revolution
Set the number of pulses per revolution for the PG being used (pulse
generator or encoder).
Default: 600 ppr
Min: 0 ppr
Max: 60000 ppr
<38>
T1-11
(70BH)
Motor Iron Loss for
Torque
Compensation
Sets the iron loss for determining the Energy Saving coefficient. The value is
set to E2-10 (motor iron loss) set when the power is re-input. If T1-02 is
changed, a default value appropriate for the motor capacity that was entered
will appear.
Default: 14 W
Min: 0 W
Max: 65535 W
<38>
CLV
V/f
OLV
CLV
V/f
OLV
MV1000ParameterGuide_E_conditional.book 75 ページ 2013年10月11日 金曜日 午後8時18分